Suction
53 - 95 PSIG
(365 to 655 kPa)
Discharge
(At Design Ambient)
280 psig (1930 kPa)
High-Pressure Cutout
400 psig (2760 kPa)
Table 2.13 Design refrigerant pressures
Input voltage
Dry Bulb Air Temperature at Condenser
Minimum
Maximum
Minimum
Maximum
-10%
+10%
-30°F (-34°C)
115°F (46°C) Std
Ambient & Quiet-Line
-5% 208/230V
single-phase
125°F (52°C)
High Ambient Models
Table 2.14 Application limits
2.6.1 Low-Voltage Control Wire Connections
Field-supplied four-wire control connection (10-wire on 8-ton units) is required between the outdoor
condensing unit and the evaporator. Refer to Figure 2.5 on page 8 ,Figure 2.7 on page 10Figure 2.8 on
page 11 and electrical schematic (Figure 2.9 on page 12 throughFigure 2.10 on page 13).
2.6.2 Low-Voltage Control Wire Sizing
Low-voltage wiring should be sized to allow a 1 volt maximum drop due to line resistance between the
evaporator and condensing unit. Use NEC Class 1 or 2 wiring according to wire routing conditions chosen,
local codes and application limits in Table 2.14 above and Table 2.15 below.
Max. Distance*
ft. (m)
Min. Wire Gauge
AWG (mm
2
)
50 (15)
20 (0.75)
100 (30)
18 (1.0)
150 (45)
16 (1.5)
* One-way control wire run between outdoor condensing unit and evaporator.
Table 2.15 Recommended minimum wire size
Vertiv
| Liebert PFH Installer/User Guide |
23
Summary of Contents for PFH020A-L
Page 3: ......
Page 74: ...Liebert Prop Fan Condensing Unit 50 Hz and 60 Hz Installer User Guide ...
Page 77: ...5 Troubleshooting 37 Vertiv Liebert PFH Installer User Guide ii ...
Page 86: ...Figure 2 6 General piping arrangement Vertiv Liebert PFH Installer User Guide 9 ...
Page 105: ...Vertiv Liebert PFH Installer User Guide 28 This page intentionally left blank ...
Page 109: ...Vertiv Liebert PFH Installer User Guide 32 This page intentionally left blank ...
Page 116: ......