2.7 Electrical Data
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage- Phase
208/230-1
208/230-3
460-3
575-3
14
1
FLA
9.1
—
—
—
WSA
11.0
—
—
—
OPD
15
—
—
—
20
1.5
FLA
12.1
—
—
—
WSA
14.8
—
—
—
OPD
25
—
—
—
27
2
FLA
13.4
—
—
—
WSA
16.4
—
—
—
OPD
25
—
—
—
37
3
FLA
18.5
13.4
7.1
5.8
WSA
22.8
16.4
8.7
7.0
OPD
35
25
15
15
42
3.5
FLA
—
15.0
7.1
6.0
WSA
—
18.4
8.7
7.2
OPD
—
30
15
15
67
5
FLA
—
24.1
11.7
9.1
WSA
—
29.3
14.2
11.1
OPD
—
45
20
15
96
8
FLA
—
36.2
18.1
13.4
WSA
—
41.4
20.6
15.3
OPD
—
60
30
20
* FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)
Table 2.16 Electrical data—Standard sound and ambient models (95°F/35°C)