Model #
Nominal
Capacity,
Tons
* Electrical
Characteristic
Input Voltage-Phase
208/230-1
208/230-3
460-3
575-3
27
2
FLA
15.4
—
—
—
WSA
18.4
—
—
—
OPD
30
—
—
—
37
3
FLA
20.5
15.4
8.1
5.8
WSA
24.8
18.4
9.7
7.0
OPD
40
30
15
15
42
3.5
FLA
—
17.0
8.1
6.0
WSA
—
20.4
9.7
7.2
OPD
—
30
15
15
67
5
FLA
—
24.2
11.7
9.3
WSA
—
29.4
14.2
11.3
OPD
—
50
20
15
* FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)
Model # 14, 20 and 96 are not available in high ambient versions.
Table 2.17 Electrical data—High ambient models (105°F/41°C) 60Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
208/230-1
208/230-3
460-3
575-3
27
2
FLA
12.9
—
—
—
WSA
15.9
—
—
—
OPD
25
—
—
—
37
3
FLA
18.0
12.9
7.1
—
WSA
22.3
15.9
8.7
—
OPD
35
25
15
—
42
3.5
FLA
—
14.5
6.9
—
WSA
—
17.9
8.5
—
OPD
—
30
15
—
67
5
FLA
—
22.5
10.9
8.3
WSA
—
27.7
13.4
10.2
OPD
—
45
20
15
* FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)
Model # 14, 20 and 96 are not available in Quiet-Line versions.
Table 2.18 Electrical data—Quiet-Line models (95°F/35°C) 60Hz
Vertiv
| Liebert PFH Installer/User Guide |
25
Summary of Contents for PFH020A-L
Page 3: ......
Page 74: ...Liebert Prop Fan Condensing Unit 50 Hz and 60 Hz Installer User Guide ...
Page 77: ...5 Troubleshooting 37 Vertiv Liebert PFH Installer User Guide ii ...
Page 86: ...Figure 2 6 General piping arrangement Vertiv Liebert PFH Installer User Guide 9 ...
Page 105: ...Vertiv Liebert PFH Installer User Guide 28 This page intentionally left blank ...
Page 109: ...Vertiv Liebert PFH Installer User Guide 32 This page intentionally left blank ...
Page 116: ......