Introduction
Liebert
®
Mini-Mate2
™
8
Location
When determining installation locations, consider that these units contain water and that water
leaks can cause damage to sensitive equipment and furniture below.
NOTICE
Risk of leaking water. Can cause equipment and building damage.
Do not mount units over equipment or furniture that can be damaged by leaking water.
Install a watertight drain pan with a drain connection beneath ducted cooling units and
ceiling mounted water/glycol condenser units. Route the drain line to a frequently used
maintenance sink so that running water can be observed and reported in a timely manner.
Post a sign to report running water from the secondary drain.
Do not install units in areas where normal unit operating sound might disturb the working
environment.