Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1
380/415-3
36
3
FLA
18.4
7.0
41
3.5
FLA
—
8.5
66
5
FLA
—
11.7
95
8
FLA
—
18.1
* FLA = Full Load Amps
Table 2.19 Electrical data—Standard sound and ambient models (95°F/35°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1
380/415-3
36
3
FLA
20.5
8.1
41
3.5
FLA
—
9.6
66
5
FLA
—
11.7
95
8
FLA
—
—
* FLA = Full Load Amps
Table 2.20 Electrical data—High ambient models
(105°F/41°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1
380/415-3
36
3
FLA
18.0
6.9
41
3.5
FLA
—
8.4
66
5
FLA
—
10.9
95
8
FLA
—
—
* FLA = Full Load Amps
Table 2.21 Electrical data—Quiet-Line models (95°F/35°C)
50Hz
2.8 Checklist for Completed Installation
1. All items unpacked and checked.
2. Proper clearances for service access maintained around equipment.
3. Equipment is level and mounting fasteners are tight.
4. Piping completed to refrigerant loop.
Vertiv
| Liebert PFH Installer/User Guide |
26
Summary of Contents for PFH020A-L
Page 3: ......
Page 74: ...Liebert Prop Fan Condensing Unit 50 Hz and 60 Hz Installer User Guide ...
Page 77: ...5 Troubleshooting 37 Vertiv Liebert PFH Installer User Guide ii ...
Page 86: ...Figure 2 6 General piping arrangement Vertiv Liebert PFH Installer User Guide 9 ...
Page 105: ...Vertiv Liebert PFH Installer User Guide 28 This page intentionally left blank ...
Page 109: ...Vertiv Liebert PFH Installer User Guide 32 This page intentionally left blank ...
Page 116: ......