PACSystems™ Industrial Displays User Manual
Section 3
GFK-3138B
Jul 2021
Hardware
71
Section 3:
Hardware
3.1
RXi - Industrial Monitor
3.1.1
Jumpers and Connectors Location
Figure 63: Jumpers and Connectors Location
Connecting Input Power (24V DC-in)
To connect to power, follow these steps:
1.
Verify that the power cable is not energized.
2.
Loosen the screw clamps on the mating power connector.
3.
Strip the insulation from the power cables.
4.
Secure the power cable to the mating connector, noting polarity,
and tighten the screw clamps. The torque for the attaching
screws is 0.3 Nm (2.26 in-lb).
5.
Apply dc power to the unit. During normal startup and operation, the LED status indicator displays
as follows:
•
Solid amber while the RXi Industrial Display unit is starting up
•
Solid green during normal operation
6.
Once power is applied, the unit begins initializing. The first thing to display is the splash screen.
Be sure to connect a DC power cord to this 3-pin power connector. Using a voltage out of the range
may fail to boot the system or cause damage to the system board.
Note: All RXi Industrial Displays are configured with reverse voltage protection to mitigate power
failure if plugged in by error.