23
IC695CPE400 Rackless CPU Quick Start Guide
GFK-3002G
Note: In the event of loss of power with the ACC403 Energy Pack
connected and charged up, the CPE400 remains on for 4 seconds to backup
user memory into its non-volatile memory.
Configuration
To configure, the CPE400, connect the computer running the PME
programming software to any of the front-panel Ethernet ports. PME 9.00
SIM 8 or later is required
The CPE400 is the first controller available in the
PACSystems RX3i Rackless
family. Configuration will either start out using the RX3i Rackless CPE400
template when creating a new project, or will convert an existing project to
the CPE400 using the
Family Conversion
feature in PME.
Backwards Compatibility
To convert an existing project which uses any other PLC, use the
Family
Conversion
feature in PME. Be aware of the constraints involved, as will be
notified in PME. For instance, the first PROFINET
®
Controller in an RX3i
CPU320 application will be assigned to the embedded PROFINET Controller
feature of the CPE400.
PROFINET Controller Configuration
An Embedded PROFINET Controller may be configured on LAN2. To enable
the PROFINET Controller in a CPE400 project, select the CPE400 target in
the
PME Navigator
(Figure 10) and open the Hardware Configuration. On the
Settings
tab, change the designated
LAN Mode
of the selected port to
PROFINET
. The
PROFINET Controller
node description then displays that a
PROFINET node exists on the selected LAN (under the CPE400). For further