background image

 

 

General Contact Information 

Please visit us for product support or updated product information: 

 
Online Technical Support  
 

https://www.emerson.com/en-us/support 

 
Additional Information: 

 

https://www.emerson.com/industrial-automation-controls

 

 
 
 
 
All Rights Reserved.  
 
We reserve the right to modify or improve the designs or specifications of the 
products mentioned in this manual at any time without notice. Emerson does not 
assume responsibility for the selection, use or maintenance of any product. 
Responsibility for proper selection, use and maintenance of any Emerson product 
remains solely with the purchaser.  
 
©2021 Emerson Electric Co.

 

 

 

Summary of Contents for PACSystems IC695CPE400

Page 1: ...PACSystems IC695CPE400 64MB Rackless CPU GFK 3002G May2021 ...

Page 2: ... 12 Field Agent Port 12 Energy Pack Connector 13 Input Power Connector 13 Removable Data Storage Device RDSD 13 Hardware Installation 14 Initial Checks 14 Installation 14 Installation in Hazardous Areas 18 Connect to Power Supply 18 Module Start up 21 Basic Start up Steps 22 Configuration 23 Start the Embedded Field Agent EFA 24 Log into the Web Console 25 Redundancy Configuration 32 Additional In...

Page 3: ...1 IC695CPE400 Rackless CPU Quick Start Guide GFK 3002G Front Panel Description Figure 1 Display Lights and Connectors on the CPE400 ...

Page 4: ... revenue and improve profitability The stand alone CPE400 uses a quad core microprocessor and real time hypervisor technology to run real time deterministic control applications concurrently with Field Agent technology without any adverse impact of one over the other o A built in RX3i PLC o User may program in Ladder Diagram Structured Text Function Block Diagram or C o Contains 64Mbytes of config...

Page 5: ... just above The embedded communications interface has dedicated processing capability which permits the CPU to independently support LAN1 and LAN2 with o up to 48 simultaneous SRTP Server connections o up to 16 simultaneous Modbus TCP Server connections o 32 Clients are permitted each may be SRTP or Modbus TCP o OPC UA Server with support for up to 5 concurrent sessions with up to 10 concurrent va...

Page 6: ... for Ethernet mode only Redundant IP is supported by the SRTP Server Modbus TCP Server and EGD protocols It is not possible to use Redundant IP with the OPC UA Server or with the Ethernet firmware update web page The CPE400 is secure by design incorporating technologies such as Trusted Platform Modules secure boot and encrypted firmware updates Optional Energy Pack IC695ACC403 allows CPE400 to ins...

Page 7: ...torage buffer for up to 128 000 events at a maximum rate of 400 events per second per PNS101 Each PNS101 supports SoE recording with IRIG B time synchronization of events accurate to 1ms and buffers up to 4000 events from up to four IC694MDL660 24Vdc 32 Point Grouped Discrete Input or IC694MDL655 24Vdc 32 Point Positive Negative Logic Input modules Unmodulated IRIG B time signals are decoded by th...

Page 8: ...enus in the OLED display SEL Permits user to select the menu item on the OLED display RUN Activates OLED Menu to select RUN Enabled or RUN Disabled Mode for the embedded PLC STOP Activates OLED Menu to select STOP Enabled or STOP Disabled Mode for the embedded PLC PHY PRES Not functional PWR Hold down for brief period to induce CPU Reset Note that this does not turn unit power off but only holds u...

Page 9: ...lay the PLC firmware revision Set view PLC mode and view sweep time Set the PLC mode to RUN STOP with I O Enabled Disabled via the display Note the RUN and STOP pushbuttons activate the PLC Mode menu items per section Switches View whether all some or none of the PROFINET I O devices are connected Display EFA Settings IPv4 address subnet mask gateway MAC address IPv6 address Issue Field Agent Comm...

Page 10: ...State Disk TEMP On Red CPU Overtemperature condition detected Off Overtemperature condition not detected OK On Green CPU has passed its power up diagnostics and is functioning properly Following initialization sequence Off Power is not applied or CPU has a problem Blinking All other LEDs off PLC in STOP Halt state possible watchdog timer fault If the programmer cannot connect cycle power with char...

Page 11: ...al faults detected IO On Green PROFINET Connection Status OK Off PROFINET Connection Status not OK RACT On Green Local Redundant CPU is Ready Active Off Local Redundant CPU is not Ready RBOK On Green Remote Redundant CPU is Ready Off Remote Redundant CPU is not Ready FAOK On Green Field Agent Running and Connected to Cloud Blinking Green Blink at 0 5 Hz Field Agent Starting Blink at 1 Hz Field Age...

Page 12: ...ower On Green Corresponding data speed is 1 Gbps or 100 Mbps Off Corresponding network data speed is 10 Mbps Bottom Ethernet Indicators EFA RJ45 Built in LED LED LED State Operating State Link Status upper On Green The corresponding link has been established Blinking Green Traffic is detected at the corresponding port Off No connection established at corresponding port Link Speed lower On Green Co...

Page 13: ...ded Ethernet interfaces automatically senses the data rate 10 Mbps or 100 Mbps or 1 Gbps communications mode half duplex or full duplex and cabling arrangement straight through or crossover of the attached link LEDs embedded in each RJ45 connector provide indications per the table above LAN1 or LAN2 may be used to communicate with the PME programming software using the Service Request Transport Pr...

Page 14: ...ocated on the underside of the CPE400 as shown in Figure 2 It provides signals for connecting either a suitable monitor or video adapter to the unit This port is not currently supported Figure 2 Underside Ports Connections Field Agent Port The RJ45 port marked EFA is located on the underside of the CPE400 as shown in Figure 2 This is an Ethernet port pre configured to connect securely to the Predi...

Page 15: ...Pack Control Status connectors shown in Figure 2 Use of the Energy Pack is optional When used it allows the CPE400 to save its current state upon loss of power Refer to the PACSystems RX3i Rackless Energy Pack IC695ACC403 Quick Start Guide GFK 3000 for complete wiring and grounding instructions Input Power Connector If no Energy Pack is to be connected refer to the section entitled Connect to Powe...

Page 16: ...are required if you should need to contact Customer Care during the warranty period All shipping containers and all packing material should be saved should it be necessary to transport or ship any part of the system Verify that all components of the system have been received and that they agree with your order If the system received does not agree with your order contact Customer Care Installation...

Page 17: ...gure 4 1 Incline the unit so that the upper hooks of the DIN rail adaptor engage with the upper edge of the DIN rail 2 Press on the lower part of the unit until you hear a click The click indicates that the lower hooks of the DIN rail adaptor have engaged with the lower edge of the DIN rail Dismount from the DIN rail per Figure 4 1 Grasp the unit securely 2 Press down on the release bar as indicat...

Page 18: ... 3002G Figure 3 Thermal Spacing Requirements 50mm 50mm 100mm 100mm Air flow adjacent device right adjacent device left adjacent device below adjacent device above 25mm Air flow max 70 C Figure 4 Mounting on DIN Rail Figure 5 Dismounting from DIN Rail ...

Page 19: ...Start Guide GFK 3002G If using the panel mount adaptor two options are available mount using two screws Figure 6 or for more secure mounting mount using four screws Figure 7 Figure 6 Two Screw Panel Mount Figure 7 Four Screw Panel Mount ...

Page 20: ... power input is the 3 pin Phoenix 1827716 shown in Figure 9 The power supply cable prepared by the user must use the specified mating connector The positive and negative signals are required FGND is optional but recommended For the mating connector the compatible conductor size is from 24AWG to 16AWG Strip the wires back 7mm before inserting into the connector Tightening torque for the three signa...

Page 21: ...rotection If and are swapped the unit will not power up If is connected to FGND this will cause a short The power supply needs to protect itself against this condition Figure 9 24 VDC Power Input Module Connector Inrush Current The CPE400 may experience an inrush current of up to 49 A for 15 µs Overvoltage protection In the CPE400 the voltage to the inner loads is clamped to 33 VDC At 33 VDC the i...

Page 22: ...Once the sensed current reaches 40A the fuse will blow after a period of 10ms to 100ms CAUTION EQUIPMENT REPAIR REQUIRED Internal components must be repaired at the factory they are not field replaceable Contact the support team at the link provided at the end of this document Grounding Grounding via the FGND connection on the 3 pin 24Vdc In power header is recommended see section Connect to Power...

Page 23: ...t using the compatible panel mount adaptor A computer running PAC Machine Edition PME configuration and programming software PME Version 9 70 SIM 16 or later supports the CPE400 Version 9 50 SIM 5 is required for Hot Standby Redundancy Ethernet cable for connecting the PME programmer computer to the CPE400 Additional cables as needed to connect each port employed in the application A very small sl...

Page 24: ...ide GFK 3000 4 Turn on the power supply unit the unit should then run without the need to press any buttons 5 If not previously configured configure the RX3i PLC using PME 9 00 SIM 8 or later as described in the Configuration section below Note When the ACC403 Energy Pack is powered up a finite period is required to charge it up to its operating level During this time the Energy Pack will indicate...

Page 25: ...CPE400 using the Family Conversion feature in PME Backwards Compatibility To convert an existing project which uses any other PLC use the Family Conversion feature in PME Be aware of the constraints involved as will be notified in PME For instance the first PROFINET Controller in an RX3i CPU320 application will be assigned to the embedded PROFINET Controller feature of the CPE400 PROFINET Controll...

Page 26: ...l GFK 2571 Figure 10 PME Navigator Showing PROFINET Node on LAN2 Start the Embedded Field Agent EFA After providing the CPE400 with power the Embedded Field Agent EFA application will begin to boot The FAOK LED will start blinking to indicate when the EFA has booted and is ready for user logins This may take about two minutes ...

Page 27: ...0 0 Set your computer s network adapter to any other IP address on the 172 31 x x network For example 172 31 0 101 with subnet mask 255 255 0 0 3 Use the OLED Menu to enable Configuration Mode as follows a From the Main Menu select the FA Settings menu item b From the FA Settings Menus select the Commands menu item c From the Commands Menus select the Config Mode menu item d Confirm entering Confi...

Page 28: ...icated by the FAOK LED and re attempt to browse to the Web Console Closing the current browser tab or window may also be required 4 Using Google Chrome recommended browse to the Field Agent s Web Console at https 172 31 0 100 8443 system console 5 Since the Web Console uses a self signed certificate the browser will warn that the connection is not private When prompted accept the connection 6 Logi...

Page 29: ...sword 9 Verify that the Log Service page displays which indicates a successful login Figure 12 Log Service Page Note After some idle time the Web Console will time out If this occurs the user will need to return to the main page to log back into the console Session timeout does not automatically redirect the console back to the login page Configure the Network EFA IP Addresses By default the Embed...

Page 30: ...hernet cable is connected to the IICS Cloud port EFA Port If a network proxy is needed to connect the field agent to the WAN refer to the section Configure a Network Proxy From the Web Console navigate to the Technician Console Network Configuration page Figure 13 Technician Console Network Configuration Page ...

Page 31: ...ture is configured to restrict access directly to the Internet Contact your network administrator for the Network Proxy information If a network HTTP HTTPS proxy server is used to route traffic from the intranet to the Internet the network proxy must be configured in the Web Console under Technician Console Network Configuration To add or update a network proxy server check the Enable HTTP HTTPS P...

Page 32: ... button after the button is pressed Otherwise a message will appear indicating that the Test Connection attempt failed Configure Time Synchronization For industrial data time stamping and Field Agent diagnostic information to operate reliably it is important for the Field Agent to have an accurate time source The Field Agent has two methods of synchronizing time either by using a Network Time Prot...

Page 33: ...the Internet exists time will be synchronized when the Field Agent boots and continuously while running The current date and time on the Field Agent is displayed above the Save button on the Time Sync Configuration page when the page loads and can be updated by pressing the Save button or reloading the page To change the NTP server to use for time synchronization enter the new NTP server URL in th...

Page 34: ... valid HTTPS URL and press the Save button If a network proxy is in use this time synchronization method will only work with HTTPS URLs that do not require a network proxy in order to reach them If the new HTTPS URL was successfully configured after pressing the Save button a success statement will be displayed and the updated time will be displayed If the time and date was more than 20 minutes ou...

Page 35: ...minimum of 5ms in both the Primary and Backup CPE400 hardware configurations The Background Window Timer setting may be found on the Scan Tab in the CPE400 s hardware configuration Once configured for HSB Redundancy the RACT and RBOK LEDs functional RACT indicates the Local CPU is Ready Active RBOK indicates the Remote CPU is Ready These two LEDs are also reflected in the Status Data of the CPU an...

Page 36: ...0 PACSystems RX3i and RSTi EP CPU Programmer s Reference Manual GFK 2950 PACSystems HART Pass Through User Manual GFK 2929 PACSystems RX3i PROFINET IO Controller User Manual GFK 2571 PROFINET I O Devices Secure Deployment Guide GFK 2904 PACSystems RX3i Rackless Energy Pack IC695ACC403 Quick Start Guide GFK 3000 IC695CPE400 RX3i 64MB Rackless CPU w Field Agent Important Product Information GFK 3003...

Page 37: ...al automation controls All Rights Reserved We reserve the right to modify or improve the designs or specifications of the products mentioned in this manual at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson product remains solely with the purchaser 2021 Emerson ...

Reviews: