11
IC695CPE400 Rackless CPU Quick Start Guide
GFK-3002G
Front-Panel Ethernet Ports
LAN1 connects to the uppermost RJ45 connector. It is not switched.
LAN2 connects to the middle two RJ45 connectors. These two ports are
switched internally.
LAN3 connects to the two lower RJ45 connectors. These two ports are
switched internally. LAN3 may only be used to supply a high-speed
synchronization link between the Primary and Secondary CPUs in Hot
Standby Redundancy. Both ports are typically used, as described in the
PACSystems Hot Standby CPU Redundancy User Manual
, GFK-2308 (revision L
or later).
Each of the embedded Ethernet interfaces automatically senses the data
rate (10 Mbps or 100 Mbps or 1 Gbps), communications mode (half-duplex
or full-duplex), and cabling arrangement (straight-through or crossover) of
the attached link. LEDs embedded in each RJ45 connector provide
indications per the table above.
LAN1 or LAN2 may be used to communicate with the PME programming
software using the Service Request Transport Protocol (SRTP).
To establish Ethernet communications between the PME programming and
configuration software and the CPU, you
first
need to know the target IP
address. Use the OLED menu function to check the IP Address. The factory-
shipped default settings are:
CPE400 LAN1
CPE400 LAN2
CPE400 LAN3
IP Address:
192.168.0.100
10.10.0.100
N/A
Subnet
Mask:
255.255.255.0
255.255.255.0
N/A
Gateway:
0.0.0.0
0.0.0.0
N/A