3
IC695CPE400 Rackless CPU Quick Start Guide
GFK-3002G
edge apps. Running the Field Agent concurrently with the real-time control
applications allows the CPE400 to rapidly leverage external data. External
monitoring may be used to analyze and optimize entire business
operations. The analysis can then be used to dynamically adjust real-time
industrial controls to align with chang
ing business objectives in today’s
Industrial Internet age.
▪
Supports four independent 10/100/1000 Ethernet LANs. Three are located
on the front panel, as shown in Figure 1. LAN1 attaches via the upper,
dedicated RJ 45 connector. LAN2 and LAN3 each attach via a pair of
internally-switched RJ 45 connectors. The fourth LAN, labeled EFA
(Embedded Field Agent), is located on the underside and is specifically used
for Field Agent connectivity (see Field Agent bullet just above).
▪
The embedded communications interface has dedicated processing
capability, which permits the CPU to independently support LAN1 and LAN2
with:
o
up to 48 simultaneous SRTP Server connections;
o
up to 16 simultaneous Modbus/TCP Server connections;
o
32 Clients are permitted; each may be SRTP or Modbus/TCP.
o
OPC UA Server with support for up to 5 concurrent sessions with up to
10 concurrent variable subscriptions and up to 12,500 variables;
o
up to 255 simultaneous Class 1 Ethernet Global Data (EGD)
exchanges.
o
DNP3 Outstation support with up to 8 master client connections
▪
The embedded PLC may use one or both of the Ethernet LAN2 ports to
support the embedded Simplex PROFINET I/O Controller. PROFINET
supports up to 32 I/O devices in simplex configuration or 20 I/O devices a in
Hot Standby Redundancy configuration, both supporting update rates of 1
–
512 ms.. I/O device update rates of 8 ms and faster are possible with 16 or
fewer devices. Update rates of 16 ms and higher result whenever more than
16 devices are configured.