Model 2400S Transmitters with Analog Outputs
Required Transmitter Configuration
6.7.2
Assignment
The discrete output can be used to report the conditions described in Table 6-18.
Flow switch
Flow switch refers to the flow rate moving past a user-configured setpoint, in either direction. For
example, if the setpoint is 100 lb/min, a flow switch occurs if the flow rate changes from 101 lb/min
to 99 lb/min, or from 99 lb/min to 101 lb/min.
Table 6-17
Discrete output polarity
Polarity
Output power supply
Description
Active high
Internal
• When asserted (condition tied to DO is true), the circuit provides
a pull-up to 24 V.
• When not asserted (condition tied to DO is false), the circuit
provides 0 V.
External
• When asserted (condition tied to DO is true), the circuit provides
a pull-up to a site-specific voltage, maximum 30 V.
• When not asserted (condition tied to DO is false), the circuit
provides 0 V.
Active low
Internal
• When asserted (condition tied to DO is true), the circuit provides
0 V.
• When not asserted (condition tied to DO is false), the circuit
provides a pull-up to 24 V.
External
• When asserted (condition tied to DO is true), the circuit provides
0 V.
• When not asserted (condition tied to DO is false), the circuit
provides a pull-up to a site-specific voltage, to a maximum of
30 V.
Table 6-18
Discrete output assignments and output levels
Assignment
ProLink II code
Communicator
code
Display
code
Condition
Discrete
output level
(1)
(1) Voltage descriptions in this column assume that Polarity is set to Active High. If Polarity is set to Active Low, the voltages are
reversed.
Discrete events 1 – 5
(see Section 8.7)
Discrete Event
x
Discrete Event
x
EVNT
x
ON
Site-specific
OFF
0 V
Flow switch
Flow Switch
Indication
Flow Switch
FL SW
ON
Site-specific
OFF
0 V
Flow direction
Forward/Reverse
Indication
Forward/Reverse
FLDIR
Forward
0 V
Reverse
Site-specific
Calibration in progress
Cal in Progress
Calibration in
progress
ZERO
ON
Site-specific
OFF
0 V
Fault
(2)
(2) Voltage descriptions for Fault assume that the fault indicator is set to Upscale. See Section 6.7.3 for more information.
Fault Condition
Indication
Fault
FAULT
ON
Site-specific
OFF
0 V
Meter verification fault
(3)
(3) Requires Smart Meter Verification.
Meter Verification
Fault
Not available
Not available
ON
Site-specific
OFF
0 V
Summary of Contents for Micro-Motion 2400S
Page 8: ...vi Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 20: ...12 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 30: ...22 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 42: ...34 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 66: ...58 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 76: ...68 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 138: ...130 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 190: ...182 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 197: ......