Micro Motion
®
Model 2400S Transmitters with Analog Outputs
Optional Configuration
8.12
Configuring device settings
The device settings are used to describe the flowmeter components. Table 8-15 lists and defines the
device settings.
Note: The HART device ID, which is displayed in some menus, can be set only once, and is usually set at the
factory to the device serial number. If the HART device ID has not been set, its value is 0.
To configure device settings:
•
Using ProLink II, see Figure C-3.
•
Using the Communicator, see Figure C-8.
Note: This functionality is not available via the display menus.
If you are entering a date:
•
With ProLink II, use the left and right arrows at the top of the calendar to select the year and
month, then click on a date.
•
With a Communicator, enter a value in the form
mm/dd/yyyy.
8.13
Configuring sensor parameters
The sensor parameters are used to describe the sensor component of your flowmeter. They are not
used in transmitter processing, and are not required. The following sensor parameters can be changed:
•
Serial number
•
Sensor material
•
Liner material
•
Flange
To configure sensor parameters:
•
Using ProLink II, see Figure C-3.
•
Using the Communicator, see Figure C-8.
Note: This functionality is not available via the display menus.
Table 8-15
Device settings
Parameter
Description
HART tag
(1)
(1) Devices using HART protocol to communicate with the transmitter may use either the HART address (see Section 8.11.1) or the
HART tag. You may configure either or both, as required by your other HART devices.
Also called the “software tag.” Used by other devices on the network to identify and communicate with
this transmitter via HART protocol. The HART tag must be unique on the network. If the transmitter
will not be accessed using HART protocol, the HART tag is not required.
Maximum length: 8 characters.
Descriptor
Any user-supplied description. Not used in transmitter processing, and not required.
Maximum length: 16 characters.
Message
Any user-supplied message. Not used in transmitter processing, and not required.
Maximum length: 32 characters.
Date
Any user-selected date. Not used in transmitter processing, and not required.
Summary of Contents for Micro-Motion 2400S
Page 8: ...vi Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 20: ...12 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 30: ...22 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 42: ...34 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 66: ...58 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 76: ...68 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 138: ...130 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 190: ...182 Micro Motion Model 2400S Transmitters with Analog Outputs ...
Page 197: ......