Specifications
31
Table 16
Electrical data, 60 Hz - amps
Model
Volts
Phase
No Heat
5 kW Heat
10 kW Heat
15 kW Heat*
Circ1
Circ2
FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
ET0187 208/230
1
14.5 17.2
25
23.4 29.3
30
44.4 55.5
60
NA
—
—
—
—
—
ET0247 208/230
1
15.2 18.1
30
23.4 29.3
30
44.4 55.5
60
NA
—
—
—
—
—
ET0247 208/230
3
11.7 13.7
20
14.4
18
20
26.4
33
35
NA
—
—
—
—
—
ET0247
460
3
5.9
6.9
15
7.3
9.1
15
13.3 16.6
20
NA
—
—
—
—
—
ET0367 208/230
1
19.5 23.4
40
23.4 29.3
40
44.4 55.5
60
44.4 55.5
60
21
26.3
30
ET0367 208/230
3
15.2 18.1
30
15.2 18.1
30
26.4
33
35
38.4
48
50
—
—
—
ET0367
460
3
7.7
9.1
15
7.7
9.1
15
13.3 16.6
20
19.3 24.1
25
—
—
—
ET0487
ET3487 208/230
1
31.9
38
50
31.9
38
50
46.2 57.8
60
46.2 57.8
60
21
26.3
30
ET0487
ET3487
208/230
3
21.9 25.5
35
21.9 25.5
35
28.2 35.3
35
40.2 50.3
60
—
—
—
ET0487
ET3487
460
3
11
12.8
20
11
12.8
20
14.1 17.6
20
20.1 25.1
30
—
—
—
ET0607
ET3607 208/230
1
37.7 45.2
60
37.7 45.2
60
46.2 57.8
60
46.2 57.8
60
21
26.3
30
ET0607
ET3607
208/230
3
28.3 33.5
50
28.3 33.5
50
28.3 35.3
50
40.2 50.3
50
—
—
—
ET0607
ET3607
460
3
13.8 16.3
25
13.8 16.3
25
14.1 17.6
25
20.1 25.1
30
—
—
—
* 15 kW heat option @ 208/230 - 1 phase requires two electrical feeds.
Circuit 1 supplies the compressor, condenser, 10 kW heat and the evaporator motor.
Circuit 2 supplies the remaining 5 kW heat.
Table 17
Electrical data, 50 Hz - amps
Model
Volts
Phase
No Heat
5 kW Heat
10 kW Heat
15 kW Heat*
Circ1
Circ2
FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
ET0357 220/240
1
17.4 20.8
35
23.4 29.3
35
44.4 55.5
60
44.4 55.5
60
21
26.3
30
ET0357 200/230
3
14.5 17.2
25
14.5
18
25
26.4
33
35
38.4
48
50
—
—
—
ET0357 380/415
3
7.7
9.1
15
8.3
10.4
15
15.3 19.1
20
22.3 27.9
30
—
—
—
ET0477
ET3477 200/230
3
21.9 25.5
35
21.9 25.5
35
28.2 35.3
35
40.2 50.3
60
—
—
—
ET0477
ET3477
380/415
3
11
12.8
20
11
12.8
20
16.1 20.1
25
23.1 28.9
30
—
—
—
EF0597
ET3597 200/230
3
28.3 33.5
50
28.3 33.5
50
28.3 35.3
50
40.2 50.3
50
—
—
—
ET0597
ET3597 380/415
3
13.8 16.3
25
13.8 16.3
25
16.1 20.1
20
23.1 28.9
30
—
—
—
* 15 kW heat option @ 220/240 - 1 phase requires two electrical feeds.
Circuit 1 supplies the compressor, condenser, 10 kW heat and the evaporator motor.
Circuit 2 supplies the remaining 5 kW heat.