Specifications
28
Table 13
Technical data, 50 Hz - High ambient condenser, continued
Model
ET047, ET347
ET059, ET359
Compressor type
Scroll
Scroll
Net capacity data based on 26.6°C (80°F) DB/19.4°C (67°F) WB indoor ambient - kW (BTUH)*
Outdoor ambient
29.4°C
(85°F)
Total
12.1 (41400)
14.6 (50000)
Sensible
8.8 (30000)
9.7 (33200)
35.0°C
(95°F)
Total
11.5 (39500)
13.8 (47400)
Sensible
8.6 (29300)
9.5 (32400)
40.6°C
(105°F)
Total
10.9 (37400)
13.1 (44700)
Sensible
8.4 (28600)
9.2 (31600)
(46.1°C)
115°F
Total
10.3 (35200)
12.4 (42200)
Sensible
8.2 (27900)
9.0 (30900)
Net capacity data based on 23.9°C (75°F) DB/16.9°C (62.5°F) WB indoor ambient - kW (BTUH)*
Outdoor Ambient
29.4°C
(85°F)
Total
11.2 (38400)
13.4 (45800)
Sensible
8.7 (29600)
9.6 (32700)
35.0°C
(95°F)
Total
10.7 (36500)
12.7 (43600)
Sensible
8.4 (28800)
9.3 (31700)
46.1°C
(115°F)**
Total
10.1 (34600)
12.2 (41600)
Sensible
8.2 (28100)
9.0 (30900)
(46.1°C)
115°F
Total
9.6 (32600)
11.5 (39300)
Sensible
8.0 (27200)
8.8 (30000)
Evaporator Air Flow - Dry Coil (Derate ESP by 0.15 - IN WG (50 Pa) for ET347 and ET359)
External Static Pressure
m
3
/hr (CFM)
0.0 Pa (0.0 - IN WG)
2870 (1690)
2870 (1690)
25 Pa (0.1 - IN WG)
2700 (1590)
2700 (1590)
50 Pa (0.2 - IN WG)
2500 (1470)
2500 (1470)
75 Pa (0.3 - IN WG)
2330 (1370)
2330 (1370)
100 Pa (0.4 - IN WG)
—
—
125 Pa (0.5 - IN WG)
—
—
Evaporator Air Flow - Wet Coil (Derate ESP by 0.15 - IN WG (50 Pa) for ET347 and ET359)
External Static Pressure
m
3
/hr (CFM)
0.0 Pa (0.0 - IN WG)
2550 (1500)
2550 (1500)
25 Pa (0.1 - IN WG)
2380 (1400)
2380 (1400)
50 Pa (0.2 - IN WG)
2240 (1320)
2240 (1320)
75 Pa (0.3 - IN WG)
2070 (1220)
2070 (1220)
100 Pa (0.4 - IN WG)
—
—
125 Pa (0.5 - IN WG)
—
—
Evaporator
Motor kW (Hp)
0.37 (0.50)
0.37 (0.50)
Filter Sizes - Quantity cm (in.)
53.3 x 92 x 5 - one
(21 x 36.25 x 2)
53.3 x 92 x 5 - one
(21 x 36.25 x 2)
Drain Connection - ID, in.
3/4
3/4
Weight - w/o Economizer, kg (lb)
213 (470)
213 (470)
Weight - with Economizer ,kg (lb)
222 (490)
222 (490)
* Based on rated airflow at 50 Pa (0.2 IN WG) external static and no outside air.
** For applications above 43°C (110°F) use high ambient option.
Summary of Contents for Liebert InteleCool 2
Page 2: ......
Page 52: ...Parts 46 Figure 7 Condenser piping assembly 2 1 4 10 7 8 9 6 Soft start device ...
Page 57: ...Parts 51 Figure 14 Soft start device To compressor capacitor 1 ...
Page 58: ...Parts 52 Notes ...