Specifications
27
Table 12
Technical data, 50 Hz - High ambient condenser
Model
ET035
Compressor type
Scroll
Net capacity data based on 26.6°C (80°F) DB/19.4°C (67°F) WB indoor ambient - kW (BTUH)*
Outdoor ambient
29.4°C
(85°F)
Total
8.6 (29200)
Sensible
6.3 (21600)
35.0°C
(95°F)
Total
8.1 (27700)
Sensible
6.2 (21100)
40.6°C
(105°F)
Total
7.6 (26000)
Sensible
6.0 (20500)
(46.1°C)
115°F
Total
7.1 (24100)
Sensible
5.8 (19800)
Net capacity data based on 23.9°C (75°F) DB 16.9°C (62.5°F) WB indoor ambient - kW (BTUH)*
Outdoor ambient
29.4°C
(85°F)
Total
7.9 (27100)
Sensible
6.3 (21400)
35.0°C
(95°F)
Total
7.5 (25600)
Sensible
6.1 (20800)
40.6°C
(105°F)
Total
7.1 (24100)
Sensible
5.9 (20200)
(46.1°C)
115°F
Total
6.5 (22300)
Sensible
5.7 (19500)
Evaporator Air Flow - Dry Coil
External Static Pressure
0.0 Pa (0.0 - IN WG)
1840 (1080)
25 Pa (0.1 - IN WG)
1730 (1020)
50 Pa (0.2 - IN WG)
1600 (940)
75 Pa (0.3 - IN WG)
1460 (860)
100 Pa (0.4 - IN WG)
—
125 Pa (0.5 - IN WG)
—
Evaporator Air Flow - Wet Coil
External Static Pressure
0.0 Pa (0.0 - IN WG)
1700 (1000)
25 Pa (0.1 - IN WG)
1590 (930)
50 Pa (0.2 - IN WG)
1460 (860)
75 Pa (0.3 - IN WG)
1330 (780)
100 Pa (0.4 - IN WG)
—
125 Pa (0.5 - IN WG)
—
Evaporator
Motor, kW (Hp)
0.19 (0.25)
Filter Sizes - Quantity, cm (in.)
16 x 32.5 x 2 - one
(40.6 x 82.5 x 5)
Drain Connection - ID, in.
3/4 (1.9)
Weight - w/o Economizer, kg (Ib)
150 (330)
Weight - with Economizer, kg (Ib)
159 (350)
* Based on rated airflow at 50 Pa (0.2 IN WG) external static and no outside air.
Summary of Contents for Liebert InteleCool 2
Page 2: ......
Page 52: ...Parts 46 Figure 7 Condenser piping assembly 2 1 4 10 7 8 9 6 Soft start device ...
Page 57: ...Parts 51 Figure 14 Soft start device To compressor capacitor 1 ...
Page 58: ...Parts 52 Notes ...
Page 59: ......