Installation
4
2.0
I
NSTALLATION
2.1
Preparation
2.1.1 Room Preparation
The room should be well-insulated and sealed to reduce airborne contaminants from penetrating the
site. Outside air may be introduced through the damper option or be used for economized cooling by
using the Economizer option. However, uncontrolled outside air should be kept to a minimum.
Outside air adds to the cooling, heating and filtration loads of the site. Doors should be properly
sealed to minimize leaks and should not contain grilles.
2.1.2 Location Considerations
The Liebert InteleCool2 unit is field-mounted on an outside wall. Additional framing in the wall may
be required to ensure adequate structural support.
The outdoor area near the condenser supply and discharge must also be considered. To assure
adequate air supply, the unit should be mounted in a clean area, away from loose dirt and foreign
matter that may clog the condenser coil. The unit should not be located near steam, hot air or fume
exhausts. Also, the unit should not be mounted closer than 12 feet (3.7 m) from an opposing wall,
obstruction or unit. For service clearance, provide 36" (914mm) in front of the unit, and 30" (762mm)
on each side. When mounting units side by side, provide a minimum of 36" (914mm) between adjacent
units unless the adjacent units will not be run at the same time. In this case, the units may be placed
as close as 18" (457mm) apart. However, this will make the units more difficult to service. In such
situations, consider the compressor location option for improved serviceability. Before mounting units,
check local codes for applicable clearances.
2.1.3 Equipment Inspection
Upon delivery of the unit, inspect all items for visible damage. Concealed damage may be discovered
later during installation. Report any damage to the shipper immediately and file a damage claim.
Also, forward a copy of the damage claim to your Emerson supplier.
2.2
Unit Installation
The Liebert InteleCool2 unit is installed against, and through, an outside wall. Two (2) openings in
the wall are required for the evaporator supply and return. Provide 1/2" clearance on wall openings
for supply and return air. Install the unit in a level position to assure proper refrigerant flow, oil
return, and condensate drain. To install the unit, follow the instructions below.
1. Verify that an adequate structural support is provided for the unit.
2. Using a chalk line, mark the outside wall with a level horizontal line, where the bottom of the unit
is to rest.
3. Prepare supply and return openings in an outside wall, measuring up from the chalk base line.
4. Prepare mounting holes. The mounting holes may be pilot holes for lag screws or clearance holes
for bolts that will extend completely through the wall. Refer to
Figure 1
for the location of these
holes.
5. Fasten the unit mounting base angle to the outside wall with six 5/16" bolts or lag screws (not
supplied), just below chalk line and centered on the opening in the wall.
6. With the unit front panel removed, lift the unit onto the base angle, making certain that the rear
unit angle falls behind the turned up front edge of the mounting angle. Insert top and side unit
fasteners in holes and tighten, drawing the unit into place.
Do not attach ducts to unit prior
to installing unit.
7. Caulk and flash the top and sides as required to form a watertight seal. Top flashing (not factory
supplied) is recommended to ensure that water does not run behind unit. All unit tops are sloped
to allow water to run off.
!
CAUTION
Risk of heavy unit—330-490 lb. (150-222 kg). Can cause serious injury.
Use caution and adequate equipment to safely handle unit.