Specifications
29
Table 14
Optional heater capacity, 60 Hz
Nominal Heater Rating
Heater Capacity - kW
1.5 Ton
2 Ton
3 Ton
4 Ton
5 Ton
5 kW
Capacity @ 208V-1ph
3.756
3.756
3.756
3.756
3.756
Capacity @ 230V-1ph
4.592
4.592
4.592
4.592
4.592
Capacity @ 240V-1ph
5.000
5.000
5.000
5.000
5.000
Capacity @ 208V-3ph
n/a
3.756
3.756
3.756
3.756
Capacity @ 230V-3ph
n/a
4.592
4.592
4.592
4.592
Capacity @ 240V-3ph
n/a
5.000
5.000
5.000
5.000
Capacity @ 460V-3ph
n/a
4.592
4.592
4.592
4.592
Capacity @ 480V-3ph
n/a
5.000
5.000
5.000
5.000
10 kW
Capacity @ 208V-1ph
7.511
7.511
7.511
7.511
7.511
Capacity @ 230V-1ph
9.184
9.184
9.184
9.184
9.184
Capacity @ 240V-1ph
10.000
10.000
10.000
10.000
10.000
Capacity @ 208V-3ph
n/a
7.511
7.511
7.511
7.511
Capacity @ 230V-3ph
n/a
9.184
9.184
9.184
9.184
Capacity @ 240V-3ph
n/a
10.000
10.000
10.000
10.000
Capacity @ 460V-3ph
n/a
9.184
9.184
9.184
9.184
Capacity @ 480V-3ph
n/a
10.000
10.000
10.000
10.000
15 kW
Capacity @ 208V-1ph
n/a
n/a
11.267
11267
11267
Capacity @ 230V-1ph
n/a
n/a
13.776
13776
13776
Capacity @ 240V-1ph
n/a
n/a
15.000
15.000
15.000
Capacity @ 208V-3ph
n/a
n/a
11.267
11.267
11.267
Capacity @ 230V-3ph
n/a
n/a
13.776
13.776
13.776
Capacity @ 240V-3ph
n/a
n/a
15.000
15.000
15.000
Capacity @ 460V-3ph
n/a
n/a
13.776
13.776
13.776
Capacity @ 480V-3ph
n/a
n/a
15.000
15.000
15.000
Summary of Contents for Liebert InteleCool 2