Operation
14
T-pack1 package
Includes a low pressure switch, low pressure bypass timer (described above) and fan cycle control.
Fan Cycle Control
—Condenser Fan Cycling Control; allows the Liebert InteleCool2 unit to provide
cooling to the space when the outdoor ambient temperature is lower than 50°F (10°C) and down to
-20°F (-28.9°C). The control uses a reverse acting pressure switch mounted on the discharge line that
cycles the condenser fan in response to the discharge pressure. On a call for cooling, when the
discharge pressure increases to 250 PSIG (1723 kPa), the switch will close and start the condenser
fan. When the pressure drips below 170 PSIG (1172 kPa) the switch will open and stop the condenser
fan. During low outdoor temperatures, the pressure switch cycles the condenser fan to maintain
discharge pressure that will allow the system to function.
T-pack2 package
Includes a low pressure switch, low pressure bypass timer and an adjustable fan cycle control. See
descriptions above.
5.4.4 Anti-Short Cycle Timer - Standard
The anti-short cycle timer protects the compressor from continuous ON-OFF operation and restarts
after momentary power failures. The timer used is adjustable and is set to a minimum of 3 minutes.
The compressor will start immediately on startup and on any call for cooling after an Off cycle of more
than 3 minutes.
5.4.5 Heater Protection - With Optional Heat
On units supplied with resistance heating, an auto reset heater safety and a one time (replaceable)
thermal link protects the unit wiring and prevents excessive heat conditions caused by a dirty air
filter or fan failure.
5.4.6 Lockout Relay - Optional
The lockout relay latches the detection of a high-pressure condition in the refrigeration circuit and
prohibits operation of the compressor until the abnormal pressure conditions are acknowledged. The
lockout relay is reset by cycling the unit main power or by changing the setpoint on the thermostat to
temporarily eliminate a call for cooling. A normally open set of contacts is provided to Terminals 2
and 3 of the customer terminal strip for monitoring the status of the lock-out relay when this option is
supplied without the Common Alarm option.
5.4.7 Common Alarm - Optional
Alarm components are an evaporator air sail switch, evaporator high temperature switch, control
relays and an adjustable time delay relay with two normally open and two normally closed alarm
contacts. The alarm contacts will activate in the event of a loss of airflow across the evaporator
blower, high evaporator temperature or in the event that the compressor is not functioning due to an
abnormal pressure condition. The adjustable time delay relay can be adjusted for a delay of up to 90
seconds to eliminate nuisance tripping of the alarm contacts. To detect low pressure, the optional low
pressure switch with bypass, T-pack1 or T-pack2 must also be selected.
NOTE
During normal operation in low ambient conditions, the condenser fan will cycle frequently.
Summary of Contents for Liebert InteleCool 2
Page 2: ......
Page 52: ...Parts 46 Figure 7 Condenser piping assembly 2 1 4 10 7 8 9 6 Soft start device ...
Page 57: ...Parts 51 Figure 14 Soft start device To compressor capacitor 1 ...
Page 58: ...Parts 52 Notes ...
Page 59: ......