Specifications
22
Table 7
Technical data, 60 Hz - Standard ambient condenser, continued
Model
ET048, ET348
ET060, ET360
Compressor Type
Scroll
Scroll
Net capacity data based on 80°F (26.6°C) DB/67°F (19.4°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
Total
47900 (14.0)
56900 (16.7)
Sensible
35400 (10.4)
38800 (11.4)
95°F
(35.0°C)
Total
45600 (13.4)
53800 (15.8)
Sensible
34600 (10.2)
37700 (11.1)
105°F
(40.6°C)
Total
43100 (12.6)
50700 (14.9)
Sensible
33800 (9.9)
36800 (10.8)
110°F
(43°C)**
Total
41800 (12.3)
48600 (14.2)
Sensible
33100 (9.7)
35800 (10.5)
Net capacity data based on 75°F (23.9°C) DB/62.5°F (16.9°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
Total
44500 (13.0)
52200 (15.3)
Sensible
35000 (10.3)
38200 (11.2)
95°F
(35.0°C)
Total
42300 (12.4)
49800 (14.6)
Sensible
34100 (10.0)
36900 (10.8)
105°F
(40.6°C)
Total
39900 (11.7)
47300 (13.9)
Sensible
33100 (9.7)
35700 (10.4)
110°F
(43°C)**
Total
38700 (11.3)
44700 (13.1)
Sensible
32600 (9.6)
34900 (10.2)
Evaporator Air Flow - Dry Coil (Derate ESP by 0.2 - IN WG (50 Pa) for ET348 and ET360)
External Static Pressure
CFM (m
3
/hr)
0.0 - IN WG (0.0 Pa)
2030 (3450)
2030 (3450)
0.1 - IN WG (25 Pa)
1910 (3240)
1910 (3240)
0.2 - IN WG (50 Pa)
1770 (3010)
1770 (3010)
0.3 - IN WG (75 Pa)
1650 (2800)
1650 (2800)
0.4 - IN WG (100 Pa)
1520 (2580)
1520 (2580)
0.5 - IN WG (125 Pa)
1390 (2360)
1390 (2360)
Evaporator Air Flow - Wet Coil (Derate ESP by 0.2 - IN WG (50 Pa) for ET348 and ET360)
External Static Pressure
CFM (m
3
/hr)
0.0 - IN WG (0.0 Pa)
1800 (3060)
1800 (3060)
0.1 - IN WG (25 Pa)
1680 (2850)
1680 (2850)
0.2 - IN WG (50 Pa)
1580 (2680)
1580 (2680)
0.3 - IN WG (75 Pa)
1470 (2500)
1470 (2500)
0.4 - IN WG (100 Pa)
1360 (2310)
1360 (2310)
0.5 - IN WG (125 Pa)
1250 (2120)
1250 (2120)
Evaporator
Motor Hp (kW)
0.50 (0.37)
0.50 (0.37)
Filter Sizes - Quantity, in. (cm)
21 x 36.25 x 2 - one
(53.3 x 92 x 5)
21 x 36.25 x 2 - one
(53.3 x 92 x 5)
Drain Connection - ID, in.
3/4
3/4
Weight - w/o Economizer, Ib/kg
470 (213)
470 (213)
Weight - with Economizer, Ib (kg)
490 (222)
490 (222)
* Based on rated airflow at 0.2 IN WG (50 Pa) external static and no outside air.
** For applications above 110°F (43°C) use high ambient option.
Summary of Contents for Liebert InteleCool 2
Page 2: ......
Page 52: ...Parts 46 Figure 7 Condenser piping assembly 2 1 4 10 7 8 9 6 Soft start device ...
Page 57: ...Parts 51 Figure 14 Soft start device To compressor capacitor 1 ...
Page 58: ...Parts 52 Notes ...
Page 59: ......