Maintenance
19
Table 4
Pressure information
Design
Pressures
psig (kPA)
Minimum
psig (kPa)
R-407C
Maximum
psig (kPa)
R-407C
Suction
35 (241)
90 (620)
Liquid (Approx.)
PSIG (kPa)
95°F (35°C) Ambient
250-290 (1723-2000)
Maximum
360-380 (2480-2618)
High Pressure Cutout
400 (2756)
Based on indoor conditions of 80°F (26.7°C), 50% RH, with clean filter(s).