Maintenance
17
Mechanical Failure
A mechanical compressor failure will not be indicated by a burned odor. The motor will attempt to
run. If you have determined that a mechanical failure has occurred, the compressor must be replaced.
Electrical Failure
An electrical failure will be indicated by a distinct pungent odor. If a severe burnout has occurred, the
oil will be black and acidic. If a burnout does occur, correct the problem that caused the burnout and
clean the system thoroughly using the proper procedure. It is important to note that successive
burnouts of the same system are usually caused by improper cleaning.
NOTICE
Risk of contaminated system. Can cause equipment damage.
Damage to a replacement compressor caused by improper system cleaning constitutes abuse
under the terms of the warranty, and the WARRANTY WILL BE VOIDED.
There are two kits that can be used with a complete compressor burnout: Sporlan System Cleaner and
Alco Dri-Kleener. Whichever kit is used, follow the manufacturer’s procedure.
!
CAUTION
Risk of caustic material. Can cause personal injury.
Avoid skin contact with the refrigerant and oils. Severe burns will result. Use long rubber
gloves when handling contaminated parts.