iPro Analog Outputs
Wiring Analog Outputs • 23
9
Wiring Analog Outputs
9.1. iPro Analog Outputs
The iPro Case Controller has six (6) opto-insulated analog outputs available along the bottom side of the device on terminals 21-30.
Because the analog outputs are opto-isolated, they must be powered separately from the case controller device by 24VAC at terminals
28-29.
Figure 9-1
- iPro Analog Output Connection
ANALOG OUTPUTS
TYPE:
Opto-insulated with separate 24VAC/DC power supply
NUMBER OF OUTPUTS:
6
TYPE OF OUTPUT:
4 fixed outputs 0-10VDC (Out1 - Out4)
2 configurable outputs 0-10VDC, 4-20mA (Out5 and Out6)
MAXIMUM LOAD:
40mA (Out1 - Out4)
20mA (Out5 and Out6) max with configured outputs 0-10VDC
400Ω max with configured outputs 4-20Ma
22Ω per live analog output
NOTES:
The electrical devices controlled by these analog outputs must be
powered separately with another transformer (do not use the same
secondary of the controller's power) in order to prevent the outputs
from malfunctioning or being damaged.
Table 9-1
- iPro Digital Output Specifications