54 • iPro Case Controller I&O Manual FM V1.01
026-1738 Rev 1
15
E2 Setup
The iPro Case Controller is capable of communicating with the E2E controller version 4.08 or above. Using the iPro Case
Controller with E2E offers benefits over using the case controller as a standalone device.
•
Reporting of case controller related alarms
•
The ability to log case controller data in an E2E logging group
•
The ability to shut down refrigeration in walk in boxes in the event of a refrigerant leak event (available if Emerson leak detection
panel is used)
•
Remote access to case controller status and programming from the E2E front panel
•
The ability to remotely access the case controllers from UltraSite32 or Site Manager
Communication between E2E and the case controller takes place over the RS485 BACnet MS/TP network. Follow the instructions in
Section 12,
The BACnet Network
to connect a case controller to the E2E network and comm plug connector. Then follow the
instructions in this chapter to set up the case controller in the E2E. An E2E has up to three COM ports that can be assigned for
BACnet MS/TP communication: COM2, COM4 and COM6 are the available RS485 ports on the E2E power interface board.
15.1. Set Up Network Ports and BACnet Settings
Before setting up an iPro Case Controller in the E2E, the port that has the BACnet MS/TP cable connected to it must be set up as a
BACnet MS/TP port.
1. Log in to the E2E with level 4 access or higher.
2. Press
Alt-M
on the keyboard to access the serial tab of the general controller info setup screens.
3. This screen will have a connection field for all available COM ports on the E2E. Highlight the COM port connection you will be
using for BACnet MS/TP and press
LOOKUP
and select
BACnet MS/TP
from the list of network types.
Figure 15-1
- Serial Setup in General Configuration
Summary of Contents for iPro
Page 1: ...iPro Case Controller Installation and Operation Manual FW Version 1 01 026 1738 Rev 1 ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 78: ...70 iPro Case Controller I O Manual FM V1 01 026 1738 Rev 1 17 Appendix iPro Connection Detail ...