48 • iPro Case Controller I&O Manual FM V1.01
026-1738 Rev 1
14.4.2. Digital Inputs
To configure digital inputs, press the T1 key from the
I/O Config
menu shown above. The DI Configuration page is now displayed.
Pressing the T1/T7 keys will scroll through the screens left/right.
Press T7 to scroll to the right to access the polarity settings.
The polarity of all 20 digital inputs is configurable to OPEN or
CLOSE. The polarity is the active state of the input. Example:
DI01P=Open, so an open signal input on digital input results in a
logical value of ON/TRUE for DI1 in the logic of the controller.
DI01P=Close, a closed signal input on digital input 1 results in a
logical value of ON/TRUE in the logic of the controller.
14.4.2.1. Digital Input Options
Figure 14-13
- DI Configuration
Figure 14-14
- DI Polarity Settings
Digital Input
Description
Hardware Available
Nu
Digital Input is
not used
N/A
Deflnit
Input to trigger
a defrost cycle
iPro or IPX
Door
Input for the
door switch
Clean
Input for the
clean switch
DualTemp
Input for the
dual
temperature
switch
Enable
Input for the
controller
enable/dis-
able
Auxiliary 1
Auxiliary input
for misc. use
Auxiliary 2
Auxiliary input
for misc. use
Table 14-2
- Digital Inputs