Commissioning the Device in E2E
iPro Parameter List • 67
EEV1_HSHd
EEV1 - High Superheat Alarm Activation Delay
0-300 Seconds
EEV1_LSHd
EEV1 - Low Superheat Alarm Activation Delay
0-300 Seconds
EEV1_PB
EEV1 - Proportional Band (if 0, Regulation Auto Adaptive) of Super-
heat
0-45°
EEV1_DB
EEV1 - Dead Band of Superheat
-50-50°
EEV1_INC
EEV1 - Integral of Superheat
0-255 Seconds
EEV1_DER
EEV1 - Derivative Superheat
0-255 Seconds
EEV1_ThrD
EEV1 - Threshold of Integral decrease
-40-90°
EEV1_PercD
EEV1 - Percentage of integral decrease below the threshold
0-100%
EEV1_ExtraCl
EEV1 - Extra valve close in case of low superheating
0-500 Steps
EEV1_MOP
EEV1 - Threshold of MOP
-90-90°
EEV1_LOP
EEV1 - Threshold of LOP
-90-90°
EEV1_MOPLOPs
EEV1 - Steps Close/Open in case of MOP/LOP
1-2500 Steps
EEV1_MOPLOPd
EEV1 - Delay activation MOP/LOP
1-300 Seconds
EEV1_DutyCycle
EEV1 - Valve Duty Cycle
0-100%
Lighting Control Parameters
LightOnHour
Scheduled time for lights on (Hour)
0-23 Hours
LightOnMin
Scheduled time for lights on (Minute)
0-59 Minutes
LightOffHour
Scheduled time for lights off (Hour)
0-23 Hours
LightOffMin
Scheduled time for lights off (Minute)
0-59 Minutes
Other Parameters
CF
Temperature Measurement Unit
°F or °C
PrU
Pressure Measurement Unit
PSI/BAR
Fty
Gas Type
R-22/R-407c/R-134a/R-404a/R-410a/
R-507/R-744 CO2/R-407a
StandaloneCC
Y=Controller is standalone (no lineup); N=Controller is in a lineup
Yes/No
S1Addr
Configuration of slave device 1 address
0-247
S2Addr
Configuration of slave device 2 address
S3Addr
Configuration of slave device 3 address
S4Addr
Configuration of slave device 4 address
S5Addr
Configuration of slave device 5 address
Modbus_Addr
Configuration of iPro itself
Baud
Baud of ModBus communication
9600/19200
MSTPMac
BACnet MS/TP MAC address
0-255
MSTPBaud
BACnet MS/TP Baud rate
9600/19200
MSTPMaxMaster
BACnet maximum master to poll for
0-127
MSTPAPDUTime
BACnet APDU Timeout value
3-60 Seconds
ExtraS_Cal_Time
Timer used for first calibration
0-480 Hours
RackID
Rack ID
See selection list
CircNum
Circuit number
1-999
CaseID
Case ID
a-i
Refrigeration Control Parameters
LTSet
Low Temperature Setpoint
-40-90°
Table 16-1
- iPro Parameter List