12 • iPro Case Controller I&O Manual FM V1.01
026-1738 Rev 1
4.6. XEV20D Valve Connections
The wires from the valve wiring harness should be terminated at the XEV20 connectors labeled
valve 1
and
valve 2
. See
Table 4-6
and
Table 4-7
below for terminal numbers associated with each valve wire color.
LED
MODE
MEANING
PWR ON
On
Tells that the model is powered correctly
ALARM
On
Tells that an alarm is present
TX/RX
Blinking
CAN Bus or LAN activity, communication activated
TX/RX
On
No link
OPEN V1
Blinking
Valve 1 is opening
OPEN V1
On
Valve 1 is completely opened
CLOSE V1
Blinking
Valve 1 is closing
CLOSE V1
On
Valve 1 is completely closed
OPEN V2
Blinking
Valve 2 is opening
OPEN V2
On
Valve 2 is completely opened
CLOSE V2
Blinking
Valve 2 is closing
CLOSE V2
On
Valve 2 is completely closed
Table 4-5
- XEV20D LED Functions
4 Wire Valves (Bipolar)
Terminal
Numbers
Alco EX
Alco EX5/6
Sporlan SEI-SHE
Sporlan CDS4-17
Danfoss ETS
Carel E2V-E7V
1
GREEN
WHITE
GREEN
GREEN
GREEN
GREEN
2
BROWN
BLACK
RED
RED
RED
YELLOW
3
YELLOW
BROWN
BLACK
BLACK
WHITE
BROWN
4
WHITE
BLUE
WHITE
WHITE
BLACK
WHITE
5 - Common
N/A
N/A
N/A
N/A
N/A
N/A
Table 4-6
- Bipolar Valve Connections
5-6 Wire Valves (Unipolar)
Terminal Numbers
Spolar
Saginomiya
EX3
1
BLACK
BLACK
BLUE
2
YELLOW
YELLOW
BLACK
3
RED
RED
BROWN
4
ORANGE
ORANGE
WHITE
5 - Common
GRAY
GRAY
GRAY
Table 4-7
- Unipolar Bipolar Valve Connections