DVC6000f Digital Valve Controllers
December 2009
C-12
Table C-3. Using PlantWeb Alerts (Continued)
PlantWeb Alert
(Group)
(Default Alert Category
Alert Condition
and (Default)
What the Alert is
Detecting
Effect on Valve / Instrument
Recommended
Action
Help
Performance Critical
(Performance)
(Failed)
Performance
Critical
(Enabled)
Critical performance issues
based on continuous PD tests
internal to the instrument.
None
−
Indicates control has
been lost or severely reduced.
Check I/P, Relay,
Valve, Actuator
or Ext. Tubing as
indicated.
On-board diagnostics
have detected a critical
performance issue that
may result in loss of
control or severe
reduction in control
performance. Check or
replace the component
indicated in the
possible cause detail.
Performance Reduced
(Performance)
(Maintenance
Performance
Reduced
(Enabled)
Reduced performance issues
based on continuous PD tests
internal to the instrument.
None
−
Indicates reduced
performance.
Check I/P, Relay,
Valve, Actuator
or Ext. Tubing as
indicated.
On-board diagnostics
have detected a
performance issue that
has reduced control
performance. Check or
replace the component
indicated in the
possible cause detail.
Performance Information
(Performance)
(Advisory)
Performance
Information
(Enabled)
Performance Information
based on continuous PD tests
internal to the instrument.
None
−
Indicates information
that may pertain to control
performance.
No action
required.
On-board diagnostics
have detected an
abnormal performance
condition. No
immediate action
required.
Table C-4. Output Block PV Status
FEATURE_SEL
PW Alarms Set PV Status
Transducer Mode,
Actual
Active PlantWeb
Alarms
AO / DO
PV Status
AO / DO
PV Substatus
AO/DO PV
Limit Substatus
(1)
Enabled
OOS
X
Bad
Device Failure
Constant
Man
X
Bad
Non-specific
Constant
Auto
Fail
Uncertain
Subnormal
Auto
Maint, no Fail
Uncertain
Non-specific
Auto
Advisory, no Fail, no Maint
Good
Advisory
Auto
None
Good
Non-Specific
Not Enabled
OOS
X
Bad
Device Failure
Constant
Man
X
Bad
Non-Specific
Constant
Auto
Fail
Good
Non-Specific
Auto
Maint, no Fail
Good
Non-Specific
Auto
Advisory, no Fail, no Maint
Good
Non-Specific
Auto
None
Good
Non-Specific
NOTES:
X
=
No Effect
1. PV limit substatus reflects only READBACK limit substatus. SP limit substatus reflects only out block rate limits.
Table C-5. Limit Sub Status
Out
Block
Transducer
Mode
In Cutoff
Region
Rate
Limited
Limit
Sub-Status
AO, DO
OOS
X
X
Constant
AO, DO
MAN
X
X
Constant
AO
AUTO
High
X
High Limited
AO
AUTO
Low
X
Low Limited
AO
AUTO
X
High
High Limited
AO
AUTO
X
Low
Low Limited
AO
AUTO
None
None
Not Limited
DO
AUTO
X
High
High Limited
DO
AUTO
X
Low
Low Limited
DO
AUTO
X
None
Not Limited
NOTE: X
=
No Effect
C
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...