DVC6000f Digital Valve Controllers
December 2009
4-130
Table 4-53. Channel Selections for the Analog Input Function Block
Channel
Parameter
(1)
Block
Index
Number
XD_SCALE Units
2
TRAVEL_TARGET
TB
49
% (1342)
3
FINAL_POSITION_VALUE
TB
17
% (1342)
4
TRAVEL
TB
34
% (1342)
5
SUPPLY_PRESS
TB
35
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
6
PRESSURE_A
TB
36
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
7
PRESSURE_B
TB
37
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
8
PRESSURE_DIFF
TB
38
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
9
DRIVE_SIGNAL
TB
53
% (1342)
10
TRAVEL_DEVIATION
TB
52
% (1342)
11
TEMPERATURE
TB
48
C (1001),
F (1002)
12
CYCLE_COUNT
TB
73
no units (1588)
13
TRAVEL_ACCUMULATION
TB
72
% (1342)
1. Refer to table 4-13 for transducer block parameter descriptions and table 4-24 for AO parameter descriptions.
Figure 4-25. Analog Input Function Block Timing Diagram
OUT (mode in man)
OUT (mode in auto)
PV
63% of Change
TIME (seconds)
FIELD_VAL
PV_FTIME
FIELDBUS-FBUS_03A
Status Handling
The AI block only gets Good Non-Specified Unlimited
or Bad Device Failure for status from the transducer.
This is reflected in FIELD_VAL.STATUS [19.1].
PV.STATUS [7.1] is the same as
FIELD_VAL.STATUS [19.1]. OUT.STATUS [8.1] can
also reflect Bad, Out of Service in addition to
PV.STATUS [7.1] values.
In the STATUS_OPTS [14] parameter, you can select
from the following options to control the status
handling:
Propagate Fail Forward—If the status from the
sensor is Bad, Device failure or Bad, Sensor failure,
propogate it to OUT without generating an alarm. The
use of these sub-status in OUT is determined by this
option. Through this option, you may determine
whether alarming (sending out an alert) will be done by
the block or propagated downstream for alarming.
Uncertain if in Manual mode—The status of the
Output is set to Uncertain when the mode is set to
Manual.
Note
1. The instrument must be in Out of
Service mode to set the status option.
2. The AI block only supports the
Uncertain if in Manual and Propagate
failure. Unsupported options are not
grayed out; they appear on the screen
in the same manner as supported
options.
Channels
Filtering
The filtering feature changes the response time of the
device to smooth variations in output readings caused
by rapid changes in input. You can adjust the filter
time constant (in seconds) using the PV_FTIME [18]
parameter. Set the filter time constant to zero to
disable the filter feature.
Signal Conversion
You can set the signal conversion type with the
Linearization Type (L_TYPE [16]) parameter. You can
view the converted signal (in percent of XD_SCALE
[10]) through the FIELD_VAL [19] parameter.
100 X (Channel Value)
−
EU *@0%
FIELD_VAL =
(EU *@100%
−
EU *@0%)
*XD_SCALE values
4
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...