F
OUNDATION
Fieldbus Communication
December 2009
D-9
Figure D-5. Unscheduled Data Transfer
B2714-1 / IL
LAS
Device X
Device Y
Device Z
PT (Z)
LAS=Link Active Scheduler
P=Publisher
S=Subscriber
PT=Pass Token
M=Message
Schedule
X
Y
Z
B
P
P
P
S
S
S
C
D
A
A
A
M
M
Host System
token, pass token (PT), is sent by the LAS to each
device in numerical order according to address.
Device Communication
Scheduled Transfers
Information is transferred between devices over the
fieldbus using three different types of communication:
Publisher/Subscriber: This type of
communication is used to transfer critical process loop
data, such as the process variable. The data
producers (publishers) post the data in a buffer that is
transmitted to the subscriber (S), when the publisher is
issued the Compel Data (CD) message from the LAS.
The buffer contains only one copy of the data. New
data completely overwrites previous data. Updates to
published data are transferred simultaneously to all
subscribers in a single broadcast. Transfers of this
type are scheduled on a precisely periodic basis.
Figure D-4 diagrams the method of scheduled data
transfer. Scheduled data transfers are typically used
for the regular cyclic transfer of process loop data
between devices on the fieldbus. Scheduled transfers
use publisher/subscriber type of reporting for data
transfer. The Link Active Scheduler maintains a list of
transmit times for all publishers in all devices that need
to be cyclically transmitted. When it is time for a
device to publish data, the LAS issues a Compel Data
(CD) message to the device. Upon receipt of the CD,
the device broadcasts or “publishes” the data to all
devices on the fieldbus. Any device that is configured
to receive the data is called a “subscriber”.
Unscheduled Transfers
Figure D-5 diagrams an unscheduled transfer.
Unscheduled transfers are used for things like
user-initiated changes, including set point changes,
mode changes, tuning changes, and upload/download.
Unscheduled transfers use either report distribution or
client/server type of reporting for transferring data.
All of the devices on the fieldbus are given a chance to
send unscheduled messages between transmissions
of scheduled data. The LAS grants permission to a
device to use the fieldbus by issuing a pass token (PT)
message to the device. When the device receives the
PT, it is allowed to send messages until it has finished
or until the “maximum token hold time” has expired,
whichever is the shorter time. The message may be
sent to a single destination or to multiple destinations.
Report Distribution: This type of
communication is used to broadcast and multicast
event and trend reports.
Client/Server: This type of communication is
used for request/ response exchanges between pairs
of devices, such as a set point change. Like Report
Distribution reporting, the transfers are queued,
unscheduled, and prioritized. Queued means the
messages are sent and received in the order
submitted for transmission, according to their priority,
without overwriting previous messages.
D
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...