Installation
December 2009
2-5
IECEx
Conditions of Certification
Intrinsically Safe, Flameproof, Type n
DVC6010f, DVC6020f, DVC6030f, and DVC6005f
Ex ia / Ex d / Ex n
1. Warning: Electrostatic charge hazard. Do not rub
or clean with solvents. To do so could result in an
explosion.
DVC6010f, DVC6020f, DVC6030f, DVC6005f,
DVC6015, DVC6025, and DVC6035
EX d / Ex n
2. Do not open while energized.
Refer to table 1-6 for additional approval information,
figures B-14 and B-17 for IECEx loop schematics and
figures B-16 and B-18 for the IECEx nameplates.
NEPSI
Notes for Safe Use of the Certified Product
Intrinsically Safe
DVC6000f digital valve controllers (designated as
controller hereafter) have been proved to be in
conformity with the requirements specified in the
national standards GB3836.1-2000 and
GB3836.4-2000 through inspections conducted by
National Supervision and Inspection Centre for
Explosion Protection and Safety of Instrumentation
(NEPSI). The Ex marking for the products is Ex ia II
CT6/T5/T4, and their Ex certificate number is
GYJ06280. When using the product, the user should
pay attention to the items stated below:
1. The correlation of approved DVC6000f digital valve
controllers in specific product type, Ex marking and
operating ambient temperature this time is as follows:
Mounting Style
Product
Type
Ex Marking
Ambient
Temperature
Integral Mounting
DVC6010f
DVC6020f
DVC6030f
Ex ia II CT6
−
40
C to
+75
C
Ex ia II CT5
−
40
C to
+80
C
Separate
Mounting
Main Unit
DVC6005f
Ex ia II CT6
−
40
C to
+75
C
Ex ia II CT5
−
40
C to
+80
C
Feedback
Unit
DVC6015
Ex ia II CT6
−
60
C to
+80
C
DVC6025
Ex ia II CT5
−
60
C to
+95
C
DVC6035
Ex ia II CT4
−
60
C to
+125
C
2. The enclosure of the controller provides a
grounding terminal, and the user should install a
reliable grounding wire connected to it when mounting
and using the controller.
3. The values for intrinsically safe parameters and
maximum internal equivalent parameters of the
controller are as follow:
Max Input
Voltage
Ui (V)
Max Input
Current
Ii (mA)
Max Input
Power
Pi (W)
Max Internal
Equivalent Parameter
Ci (nF)
Li (mH)
24
226
1.4
5
0
17.5
380
5.32
5
0
4. As a main unit of a separate design product, the
values for intrinsically safe output parameters of
DVC6005f are as follows:
Max Output
Voltage
Uo (V)
Max Output
Current
Io (mA)
Max Output
Power
Po (mW)
Max Equivalent
Parameter allowed
Co (
m
F)
Lo (mH)
8.6
2.3
5
8.2
100
5. While the controller forms an intrinsically safe
explosion protection system together with an
associated equipment, the following requirements
must be met: Uo
v
Ui, Io
v
Ii, Po
v
Pi, Co
w
Ci + Cc,
Lo
w
Li + Lc.
Note
Where Cc and Lc represent distributing
capacitance and inductance of the
connecting cable respectively.
6. The connection cable between the product and
associated equipment should be a cable with
insulation screen and sheath. The screen should be
connected to the ground.
2
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...