Product data sheet
FieldQ
FieldQ
Copyright © Emerson. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website
www.emerson.com/fieldq or from your Emerson Automation Solutions - Actuation Technologies Center:
America’s:
+1 281 477 4100
Europe:
+36 22 53 0950
Asia/Pacific:
+65 67 77 8211
1.607.01 Rev. 2 Page 5 of 8
March 2019
Metric Model String Configuration
QC40 with ASI Digital Bus Communication
QC40
-
M WP G S A 1
-
0040 I NS 0 IP 0 0
Control module
Conduit connections
Protection method
Control module options
Action
Future Expansions
Language
Bottom electrical entry
Top electrical entry
Pneumatic exhaust
Manual Control
Speed control
Mounting Options
IPT Device size actuator
Control module
IPT Device size for actuator:
QC40
Control module with AS-I communication
0040
Q40 actuator
Connections
0065
Q65 actuator
M
Metric: Conduit: 2x M20x1.5 - Pneumatic: 1/4" BSP
0100
Q100 actuator
Protection method
0150
Q150 actuator
WP
Weather Proof IP66/NEMA4X
0200
Q200 actuator
P4
Non Sparking - Ex nA / Ex tb - ATEX, IECEx
0350
Q350 actuator
B4
Non Sparking Ex nA / Ex tb - INMETRO/Brazil
0600
Q600 actuator
F4
Non Incendive N.I. - FM
0950
Q950 actuator
C4
Non Incendive N.I. - CSA
1600
Q1600 actuator
Control module options (position feedback)
0000
No IPT probe
G
Mechanical switch (Gold Plated)
Mounting Options
N
2-wire prox. switch (NAMUR)
U
Uninstalled
Action
I
Installed/Tested to actuator
S
Single acting (Spring Return)
Speed control
D
Double acting
NS
No Speed Control
F
Double acting Fail "In Last Position"
N1
Spring Return (1x throttle)
Future Expansions Code
N2
Double acting (2x throttle)
K
Standard Yellow
Manual Control
Language Code
0
No Manual Control
1
English
1
1x "Push&Lock", anodized aluminum
2
Portuguese
2
2x "Push&Lock", anodized aluminum
3
French
3
1x "Push&Lock", Stainless Steel
4
2x "Push&Lock", Stainless Steel
Pneumatic exhaust
IP
IP65/NEMA4 rated exhaust
IN
Non metalic exhaust / Check valve
Top conduit (Glands & Plugs, note 3)
0
Transport plug
1
Metal blind plug
4
Eurofast (M12)
5
Minifast (7/8”)
Bottom conduit (Glands & Plugs, note 3)
0
Transport plug
1
Metal blind plug
4
Eurofast (M12)
5
Minifast (7/8”)
Notes:
1.
For more detailed information on hazardous area protection methods, certification agencies and suitable hazardous area see section
Selection guide Q-Series Control Module certifications
on page 2.
- For QCQ40 and QC54 control modules: CSA Approval only for class II and III
- For QCQ40 control modules: Switch type “G” is only available with protection code “F4” and “WP”
2.
2x Manual Control are only required in case of Double acting with Fail in Last Position function.
3.
For QC40 and QC54: Quick Connector options are only available with QC40 (ASI) and QC54 (FF). Prices for Glands & Plugs are per piece.
The Quick Connectors, as listed, are excluded from areas with a potential explosion hazard caused by gasses, dust or fibers.
4.
No separate pneumatic module required. Pneumatic function is integrated in the module.
5.
For applications below -20°C (-4°F), the base actuator must be fitted with Low Temperature seals.
For use in atmospheres with a potential explosion hazard, the minimum temperature is -25°C / -13°F.