Product data sheet
FieldQ
FieldQ
Copyright © Emerson. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website
www.emerson.com/fieldq or from your Emerson Automation Solutions - Actuation Technologies Center:
America’s:
+1 281 477 4100
Europe:
+36 22 53 0950
Asia/Pacific:
+65 67 77 8211
1.604.12 Rev. 3 Page 11 of 13
November 2018
Diagnostics and PlantWeb Alerts
Alerts & recommended actions
Alerts
Alert default setting
Advisory
Maintenance
Fail
Parameter name
DeltaV text
Recommended actions
en
ab
le
m
as
k
(sh
ow)
en
ab
le
m
as
k
(sh
ow)
en
ab
le
m
as
k
(sh
ow)
Internal alerts
bad_position_sensor
Bad Position Sensor Error
Feedback problem, replace control module
when possible
n
n
y
y
n
n
bad_temperature_sensor
Bad Temperature Sensor
Error
Temperature sensor problem, replace Control
module when possible
n
n
y
y
n
n
system_temperature_exceeded System Temperature
Exceeded
Take corrective actions to bring temperature
within specified range.
n
n
y
y
n
n
software_error
Software Error
Software error has been detected, replace
control module when possible.
n
n
y
n
n
n
travel_deviation
Travel Deviation
Lost position, Check air pressure
y
y
n
n
n
n
shutdown_is_set
Shutdown Is Set
Internal communications problem, check
shutdown configuration for restart, Replace
Control module.
n
n
n
n
y
y
pilot valve_error
Pilot valve error
pilot valve number mismatch or pilot valve
failure has been detected
n
n
y
y
n
n
Buttonboard_error
Buttonboard Error
Error is undefined, replace control module
when possible
n
n
y
n
n
n
Counter alerts
cm_life_exceeded
Control Module Life Cycle
Exceeded
Control module life cycle exceeded, replace
control module
n
n
y
y
n
n
pm_life_exceeded
Pneumatic Module Life
Cycle Exceeded
Pneumatic module life cycle exceeded,
replace pneumatic module.
n
n
n
n
n
n
act_life_exceeded
Actuator Life Cycle Ex-
ceeded
Actuator life cycle exceeded, replace actuator.
n
n
n
n
n
n
valve_life_exceeded
Valve Life Cycle Exceeded
Valve life cycle exceeded,valve requires
maintenance.
n
n
n
n
n
n
Timer alerts
time_in_position_exceeded
Time in position exceeded Time in position exceeded, take appropriate
action.
n
n
n
n
n
n
open_travel_time_exceeded
Open travel timer ex-
ceeded
Open travel timer exceeded, check valve
system.
n
n
n
n
n
n
close_travel_time_exceeded
Close travel timer ex-
ceeded
Close travel timer exceeded, check valve
system.
n
n
n
n
n
n
Initialization alert
assembly error
Assembly error
pneumatic function mismatch, check module
and actuator configuration
n
n
y
y
n
n
initialization_failed
Initialization Failure
Device failed initialization; Check airpressure,
check actuator sizing, check valve system
y
y
n
n
n
n