Product data sheet
FieldQ
FieldQ
Copyright © Emerson. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website
www.emerson.com/fieldq or from your Emerson Automation Solutions - Actuation Technologies Center:
America’s:
+1 281 477 4100
Europe:
+36 22 53 0950
Asia/Pacific:
+65 67 77 8211
Hazardous area executions
Control Module QC54 with FOUNDATION™ Fieldbus is available with optional intrinsically safe (IS) or Non-Incendive/
Non Sparking (NI) approvals as listed below:
IECEx
Certificate No.:
IECEx DEK16.0006X
Intrinsically safe*
Ex ia IIC T4 Ga
Ex ia IIIC T80°C Da
Ex ic IIC T4 Gc
Non-Sparking
Ex nA IIC T4 Gc
Ex tb IIIC T80°C Db
ATEX
Certificate No.:
DEKRA 16ATEX0006X
Intrinsically safe*
II 1 G Ex ia IIC T4 Ga
II 1 D Ex ia IIIC T80°C Da
II 3 G Ex ic IIC T4 Gc
Non-Sparking
II 2 D Ex tb IIIC T80°C Db
II 3 G Ex nA IIC T4 Gc
FM
Certificate No.:
FM16US0366X
Type 4X
Intrinsically safe*
-
Intrinsically safe,Class I, II, III Div.1,
Groups ABCDEFG, T4,
Type4/IP66
-
Class 1, Zone 1, AEx ia IIC T4
Non Incendive
-
Class I, II, III, Division 2,
Groups ABCDFG, T4,
-
Class 1, Zone 2, Group IIC T4
1.604.12 Rev. 3 Page 9 of 13
November 2018
CSA
Certificate No.:
CSA 17CA70167494X
Intrinsically safe *
Class I, Division 1, Groups A, B, C and D T4;
Class I, Division 2, Groups A, B, C and D, T4;
Class II, Division 1, Group E, F and G, T80°C;
Class III, Division 1, T80°C
Ex ia IIC T4 Ga
Ex ia IIIC T80°C Da
Ex ic IIC T4 Gc
Non Incendive
Class I, Division 2, Groups A, B, C and D, T4;
Class II, Division 1, Group E, F and G, T80°C;
Class III, Division 1, T80°C
Ex nA IIC T4 Gc
Ex tb IIIC T80°C Db
INMETRO
Certificado: IEx 17.0085X
Intrinsically safe*
Ex ia IIC T4 Ga IP66
Ex ia IIIC T80 °C Da IP66
Certificate No.: IEx 17.0085X
Non Incendive
Ex nA IIC T4 Gc IP66
Ex tb IIIC T80 °C Db IP66
Ambient temperature:
T4 @ Ta = -20°C...+50°C IP66/nema 4x
Note:
* The assembly of a Q-Series Actuator with the intrinsically
safe QC54 Control Module, may be used in (ATEX) classified
Zones 1, 2(Gasses) and/or 21, 22 dust(Dust).
FISCO systems
The Q-Series QC54 is suitable for use in a FISCO system in
accordance with IEC 60079-27