Hourly log
Section 6: Archive logs
3410 Series Gas Ultrasonic Meters Operations Manual
January 2018
3-9000-777 Rev E
6.1.2
Hourly log
The Daniel 3410 Series Gas Ultrasonic Flow Meter meter stores an hourly log record once per
hour on the hour. The meter can store up to 2400 hourly records (100 days’ worth). The user can
select whether old, unread records can be overwritten by new records when the log becomes
full via the data point
DoOverwriteUnreadHourlyLog
. This point can be modified using the Daniel
MeterLink
Tools - Edit/Compare Configuration
screen. The default is to overwrite old, unread
records. Refer to
“Options for reading daily and/or hourly log records”
for information on
reading records and marking records as read. The data point
IsHourlyLogFull
indicates whether
or not the hourly log is full and cannot overwrite old, unread records.
The data points included in the hourly log and the corresponding log action are as shown in the
table below. Data points required by the API Chapter 21 standard are marked with an
asterisk (*). For information on a
particular
data point, consult Daniel MeterLink online help.
Table 6-2 Hourly log action type
Data point
Log action
PosVolFlow
*
Totalize and Snapshot
NegVolFlow
*
Totalize and Snapshot
PosVolBase
Totalize and Snapshot
NegVolBase
Totalize and Snapshot
FlowTemperature
*
Flow-Gated
FlowPressure
*
Flow-Gated
AbsFlowPressure
*
Flow-Gated
AccumFlowTime
*
Totalize
AvgSndVel
*
Flow-Gated
PrevDayMacro1
*
:
Macro
bit 31-30
bit 29
bits 28-25
bit 24
bit 23
bit 22
bit 21
bit 20
bit 19
bit 18
bits 17-0
(unused)
DI1
(unused)
IsAcqModuleError
DidPowerFail
DidCnfgChksumChg
IsElecTempOutOfRange
IsElecVoltOutOfRange
IsGCAlarmPresent
IsGCCommErr
(unused)