Installation and Operation Manual
E2K-405-0218 Rev. 2
February 2018
3
Section 2: Quick Start
Quick Start
Section 2: Quick Start
The
Quick Start Section
provides step-by-step instructions for initializing the TEC2
actuator. When these instructions are complete, the position limits will be set and the
actuator will be ready for normal operation.
NOTE:
The actuator has been configured as specified by the customer and no further changes
should be required. If full valve data was not provided, actuator will be shipped with
default configuration per
Table 4.4
,
Default Configuration Settings
, unless specific
configuration was requested.
WARNING:
Use caution when working on, with, or around valves and actuators.
High pressures, forces, voltages, and flammable media can be present.
WARNING:
Verify voltage rating on nameplate before connecting power.
2.1
Set Position Limits
1)
Power actuator. The alarm message “
SET LIMITS BEFORE OPERATING
” will be
displayed. The alarm icon and the yellow LED will be flashing. Valve position will be
displayed as “
EE
%”.
2)
The instruction is based on valve being in closed position. If valve is at
"Open"
end of travel, you must move the valve in
"Close"
direction and set a dummy
close limit. Then move back to
"Open"
and set the open limit. Save the limits.
Proceed as follows to set the limits. See
Section 5.5.3, Set Valve Travel Limits
for additional details.
A)
Enter the “
SETUP
” mode.
1)
Place the selector knob in the
STOP
position.
2)
Rotate the control knob to
YES
, then
NO
, then
YES
, then
NO
in
rapid succession and then release. The Setup icon will be displayed
on the display module and “
SETUP?
” will be displayed on the
message center.
3)
Rotate the control knob to
YES
. “
SET LIMITS BEFORE
OPERATING
” will be displayed on the message center.
4)
Rotate the control knob to the
LOCAL
position. The message
“
CLOSE VALVE THEN SELECT STOP
” will be displayed.
B)
Set close valve travel limit.