Installation and Operation Manual
E2K-405-0218 Rev. 2
February 2018
53
Section 5: Customizing Actuator Settings
Customizing Actuator Settings
5.5.5 Discrete Output Setup
Relay outputs are used primarily for hard wired status feedback. Each relay
may be configured (assigned) to various status, alarm, or control functions.
Relay outputs can be configured to be active on the listed alarms/conditions.
Relay outputs #1 through #5 are standard and may be configured as shown in
Table 5-1
. Configurable functions are listed in
Table 5-2
.
To configure the relays:
1.
At the
“DISCRETE OUTPUT SETUP?”
prompt answer
“YES.”
2.
Use the selector knob
(NEXT/BACK)
to review the settings for Discrete
Outputs.
3.
Use the control knob
(NO)
to select desired configuration for each relay.
See
Figure 5-10.
Table 5-1.
Relay Outputs #1 through #5 Configuration
Relay
Default
Function
Configu-
rable
Function
Configure
N.O./N.C.
Default
Setting
Configure
Flashing
RO#1
LSO
Valve full
OPEN
See
Table 5-2
Relay Output
Function List
Yes
N.O.
Yes
RO#2
LSC
Valve full
CLOSE
See
Table 5-2
Relay Output
Function List
Yes
N.O.
Yes
RO#3
LSO
Valve Full
Open
See
Table 5-2
Relay Output
Function List
Yes
N.O.
Yes
RO#4
LSC
Valve Full
Close
See
Table 5-2
Relay Output
Function List
Yes
N.O.
Yes
RO#5
Monitor
Valve not
available
Host Control
–
see NOTE
No
1 N.O. and
1 N.C.
Yes