Installation and Operation Manual
E2K-405-0218 Rev. 2
February 2018
35
Section 4: Operation
Operation
Two-Speed Timer Default Configuration
Close
Open
Anti-Water Hammer
Mode = OFF
Mode = OFF
Mode = OFF
Start Position = 30%
Start Position = 70%
Start Position = 10%
Stop Position = 1%
Stop Position = 99%
Pulse ON time = 3.5 Sec
Pulse ON time = 3.5 Sec
Pulse ON time = 3.5 Sec
Pulse OFF time = 5.0 Sec
Pulse OFF time = 5.0 Sec
Pulse OFF time = 5.0 Sec
Auxiliary Control Module (ACM) Default Configuration
Analog Control - Futronic
Network Control - Controlinc
Control Bandwidth = 2.0%
Network Node Address = 001
Speed Bandwidth = 5.0%
Response Delay Time = 8ms
Delay Time = 1 Second
Parity = NONE
Input Polarity CLOSE = 4mA
Analog I/0 Scale 0 - 4095
Output Polarity CLOSE = 4mA
Write Protect = NO
STAYPUT on lost signal
1.
Enter “
SETUP
” mode as detailed in
Step No 2
of
Section 2, Quick Start
.
2.
Place the selector knob in the NEXT position to advance through each
display until “
DISPLAY SETTINGS?
” is displayed.
3.
Rotate the control knob to
YES
.
4.
Scan through each display selecting
NO
or
YES
and
BACK
or
NEXT
as
needed to review the current settings. See
Figure 4-4
.
NOTE:
The “
DISPLAY SETTINGS?
” mode can be accessed without entering a passcode;
however no changes can be made to the settings in this mode. To make any
changes see
Section 5, Customizing Actuator Settings
.