Installation and Operation Manual
E2K-405-0218 Rev. 2
56
Section 5: Customizing Actuator Settings
Customizing Actuator Settings
Relays #9 through #12 are the auxiliary relays when the Auxiliary Relay Module
(ARM) is installed. To configure these relay outputs, follow Step No.1 through
No. 3 listed above. See
Table 5-3.
NOTE:
The ARM cannot be added when the Controlinc ACM is installed.
Table 5-3.
Relay Outputs #9 through #12 Configuration
Relay
Default
Function
Configurable
Function
Configure
N.O./N.C.
Default
Setting
RO#9
Lost Power
See
Table 5-2 Relay
Output Function List
Yes
N.O.
RO#10
Motor Overload
See
Table 5-2 Relay
Output Function List
Yes
N.O.
RO#11
Lost Phase
See
Table 5-2 Relay
Output Function List
Yes
N.O.
RO#12
Over Torque
See
Table 5-2 Relay
Output Function List
Yes
N.O.
5.5.6 Inhibit and ESD Setup
1.
At the
“INHIBIT AND ESD SETUP?”
prompt answer
“YES.”
2.
Use the selector knob (
NEXT/BACK
) to review the settings for Control
Inhibits and Emergency Shut Down.
3.
Use the control knob (
NO
) to select either
ON
or
OFF
for each setting;
then answer “
YES.
”
Figure 5-11
details each setting.