February 2018
Installation and Operation Manual
E2K-405-0218 Rev. 2
40
Section 5: Customizing Actuator Settings
Customizing Actuator Settings
Section 5: Customizing Actuator Settings
5.1
Entering Setup Mode
The “
SETUP
” mode must be entered to modify any configuration settings.
1.
Place the selector knob in the
STOP
position. Setup may be performed at any one
location; i.e. at the LDM or any RDM that is connected.
NOTE:
STOP
button on the Clicker only stops a moving valve.
2.
Rotate the control knob to
YES
, then
NO
, then
YES
, then
NO
in rapid succession
and then release. “
SETUP
” icon will be displayed on the display module and
“
SETUP?
” will be displayed on the message center.
NOTE:
Do not hold the knob in any one position longer than 0.5 seconds.
3.
Rotate the control knob to
YES
. A series of questions will be displayed as detailed
in
Figure 5-1
.
NOTE:
If the control knob is placed in the
NO
position or if
NEXT
or
BACK
is selected in
lieu of
YES
, the display will return to the normal display mode.
4.
Use the control knob to answer “
YES
” or “
NO
” to the displayed questions.
Use the selector knob,
NEXT
and
BACK
, to advance through the setup selections.
5.
When configuring is complete, advance to “
EXIT SETUP?
” Answer “
YES.
”
The display will return to normal display model.
NOTE:
If a knob entry is not made within 120 seconds, the actuator will exit the “
SETUP
” mode
and revert to the normal display.
NOTE:
No Passcode is required for viewing any of the settings.
Passcode will be needed for changing any of the parameters.