4 • High Pressure CO2 Controller Installation and Operation Manual
2.2
Inputs and Outputs
Digital relay outputs
4 NO relays, 2 common
Digital relay outputs
4 NO relays, 2 common
Connector
Description
Table 2-1
- Connections and Descriptions
Input
Number
Type of
Input
Description
1
Supply
Reference “-“/Common power (24VAC or 24VDC)
2
Pb1
Configurable analog input 1 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
3
Pb2
Configurable analog input 2 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
4
Pb3
Configurable analog input 3 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
5
+12V
Additional power +12VDC
6
+5V
Additional power +5VDC
7
Out1
Analog output 1, 0 - 10V, 4 - 20mA, Relay
8
Out2
Analog output 2, 0 - 10V, 4 - 20mA, Relay
9
Supply
Reference “+” power supply (24VAC or 24VDC)
10
Pb4
Configurable analog input 4 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
11
Pb5
Configurable analog input 5 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
12
Pb6
Configurable analog input 6 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
13
PbC
Common analog inputs (NTC, PTC, DI)
14
Voltage
Common
(-)
Additional power reference 5VDC and 12VDC, analog inputs
(0 - 20mA, 4 - 20mA, 0 -10V, 0- 1V, 0 - 5V), analog outputs
15
Out3
Analog output 3, 0 - 10V, 4 - 20mA, Relay
16
Out4
Analog output 4, 0 - 10V, 4 - 20mA, Relay
20
DI1
Digital input 1, 24VAC/DC
28 DI9 29 DI10 30 DI11
21
DI2
Digital input 2, 24VAC/DC
Table 2-2
- Description of the Inputs and Outputs
Summary of Contents for 818-9010
Page 1: ...026 1731 Rev 0 01 DEC 2014 High Pressure CO2 Controller Installation and Operation Manual ...
Page 2: ......
Page 4: ......
Page 19: ...Figure 3 1 MODBUS Networking 13 ...
Page 45: ...Figure 10 29 Override Screen 39 ...
Page 49: ...Figure 12 2 High Pressure CO2 Device Wiring and Network Connection 43 ...