16 • High Pressure CO2 Controller Installation and Operation Manual
Press ENTER to save new address.The address
field should stop blinking.
Press
T1
(MENU) to go back to the previous
menu.
NOTE: When the MODBUS address is
changed, the High Pressure CO2 controller
needs to be rebooted.
3.1.2.4
Versions
The High Pressure CO2 controller and Visograph ver-
sions are also shown on the Controller Info screen.
To see the High Pressure CO2 controller version,
please see the
Visograph
Section of the Status screen.
3.2
MODBUS Termination
If the High Pressure CO2 controller is located at the
physical end of the MODBUS network, install the MOD-
BUS termination block
(P/N 537-2711)
.
Summary of Contents for 818-9010
Page 1: ...026 1731 Rev 0 01 DEC 2014 High Pressure CO2 Controller Installation and Operation Manual ...
Page 2: ......
Page 4: ......
Page 19: ...Figure 3 1 MODBUS Networking 13 ...
Page 45: ...Figure 10 29 Override Screen 39 ...
Page 49: ...Figure 12 2 High Pressure CO2 Device Wiring and Network Connection 43 ...