42 • High Pressure CO2 Controller Installation and Operation Manual
12 XEV20D Setup and Network
Connection
The XEV20D is a stepper valve driver that can drive a bipolar stepper valve or unipolar stepper valve. It is a dummy
voltage chopper constant current driver that will be controlled by the High Pressure CO2 controller through a LAN com-
munication network. It can control the High Pressure Valve function and/or the Bypass Gas Valve function. The user has
the option to use this driver or use the 0-10 voltage output from the High Pressure CO2 controller to another driver for
controlling the valve. If this driver is preferred, please check the manufacturer valve technical specifications for the cur-
rent ratings and verify if the XEV20D is capable of driving the valve. The XEV20D address will have to be set to 1 to
communicate with the High Pressure CO2 controller.
CAUTION! GND is Common (-), not earth
ground. Do not earth ground this device.
Figure 12-1
- High Pressure CO2 Device Wiring and Network Connection