• 35
press T1 + T3 + T8 button together and hold it until you
see the Configuration screen.
Configuration Screen:
Figure 10-9
- Configuration Screen
From this screen, you can select to configure the Gen-
eral Config, Valve Config, IO Config and XEV20D Con-
fig. Highlight the status screen to view and press T4 for
ENTER.
10.2.2 General Configuration
Screens
From the Configuration Screens, the user will have the
ability to configure the MODBUS address, baud rate,
screens up- date, time and date, temp Sensor type (Emer-
son Retail Solutions or Dixell), engineering units, pressure
transducer settings, shutdown delay and the factory default
reset.
Note: Before connecting the High Pressure CO2
Controller to E2, please make these preference changes
since it will not be available through E2 once the device is
online and configuration can only be made via E2 once
online.
The General Config Screen:
Figure 10-10
- General Config Screen 1
Press T5 button (down arrow) to highlight the parame-
ter you wish to change. Press T4 SET to edit the value.
Once the parameter is flashing, press the T3 button or T5
button to change value and press T4 SET again to submit
the change. To see additional parameters in the General
Config screen, press the T8 button (right arrow).
General Configuration Additional Screen:
Figure 10-11
- General Config Additional Screen
Press the T5 button (down arrow) to highlight the
parameter you wish to change. Press T4 SET to edit the
value. Once the parameter is flashing, press the T3 button
or T5 button to change the value and press T4 SET again
to submit the change. To go back to the other General
Config screen, press the T3 button (left arrow) or press T1
button EXIT to exit back to the main Configuration
screen.
10.2.3 Valve Configuration Screens
From the Configuration Screens, the user will have the
ability to configure the setpoints, PID settings, safety set-
tings, and the calibration feature for the HPV and BGV.
Valve Configuration Screen:
Figure 10-12
- Valve Config Screen
Press the T5 button (down arrow) to high the parame-
ter you wish to change. Press T4 SET to edit the value.
Once the parameter is flashing, press the T3 button or T5
button to change value and press T4 SET again to submit
change. To see additional parameters in the Valve Config
screen, press T8 button (right arrow). Once in the addi-
Summary of Contents for 818-9010
Page 1: ...026 1731 Rev 0 01 DEC 2014 High Pressure CO2 Controller Installation and Operation Manual ...
Page 2: ......
Page 4: ......
Page 19: ...Figure 3 1 MODBUS Networking 13 ...
Page 45: ...Figure 10 29 Override Screen 39 ...
Page 49: ...Figure 12 2 High Pressure CO2 Device Wiring and Network Connection 43 ...