10 • High Pressure CO2 Controller Installation and Operation Manual
2.3.7
Electrical Specifications
Table 2-7
- Electrical Specifications
Power Supply:
24VAC +10/-15%, 50/60Hz, 20 -
36VDC
Consumption:
From 30VA (VAC), From 25W
(VDC)
Connectors:
Molex connectors with low
voltage wiring (for IPS100D and
IPS400D)
Phoenix quick coupling
connectors for low voltage (for
IPS200D)
STELVIO 90° screw connectors
for digital outputs (250VAC, 6A
max)
Microprocessor:
AT91SAM9260 32-bit 200Mhz
Permanent
FLASH
memory:
16Mb, in 8-bit chunks
RAM:
2x128Kb, in 16-bit chunks
Internal clock:
Standard
2.3.8
Plastic Enclosure
Table 2-8
- Enclosure Specifications
Mount:
On a DIN rail (EN 50022, DIN
43880)
Fastened with screws via the
removable plastic flaps.
Material:
PC-ABS Thermoplastic
Self-
extinguishing:
V0 (UL94)
Comparative
Tracking
Index (CTI):
300V
Color:
Black or White, depending on the
model
2.3.9
USB-Ethernet Adapter
The IPS range of programmable controllers can be
connected to a computer via an external adapter. This
adapter must be used in the processing environment
for the application download in the controller. This
adapter is not set up for fixed or continuous connec-
tion. If the adapter should be kept connected continu-
ously, the room temperature must not exceed 50°C
(122°F).
Figure 2-4
- USB-Ethernet Adapter
2.4
Powering the High
Pressure CO2
Controller
Retail Solutions supplies a wide variety of 24VAC
transformers with varying sizes without center taps.
shows the transformer sizes and are non-
center-tapped.
2.4.1
Choosing Transformer Sizes
The transformer used to power the High Pressure
CO2 controller should have at least a 30VA rating.
The High Pressure CO2 controller should not share a
transformer with any other devices.
how to wire the transformer to the High Pressure CO2
controller.
Table 2-9
- Compatible Transformers with CO2 Controller
Transformer P/N
VA Rating
Primary
Voltage
640-0041
50 VA
110 VAC
640-0042
50 VA
220 VAC
Summary of Contents for 818-9010
Page 1: ...026 1731 Rev 0 01 DEC 2014 High Pressure CO2 Controller Installation and Operation Manual ...
Page 2: ......
Page 4: ......
Page 19: ...Figure 3 1 MODBUS Networking 13 ...
Page 45: ...Figure 10 29 Override Screen 39 ...
Page 49: ...Figure 12 2 High Pressure CO2 Device Wiring and Network Connection 43 ...