46
Parameter setting
Actuator KNX S1R-B4 compact
• Version: 12.09.2022 • from application 1.0 • Technical changes and errors excepted.
Staircase lighting timer
The staircase time switch sets with a time basis and time factor how long the light will
remain on (e.g. 1 s × 10 corresponds to 10 seconds). Additionally it is specified if the
time interval for a repeat receipt of a switch-on telegram is extended ("triggered again",
e.g. by pressing the button again) and what happens when a switch off telegram
arrives from the bus.
5.2.3.3.Blocking function (switch functions)
The menu item "blocking function" appears only for the settings for the switch function
channel if selected "Use blocking functions: Yes".
The output channel can be blocked by a block telegram. What happens during the
blocking, for bus voltage return and after the blocking is set here. The manual
operation is then not possible for an active block.
The function can be used for example for a light, which is turned on when pressing a
"panic button" (=trigger for blocking function) and cannot be turned off any longer.
5.2.3.4.Button input (switch functions)
The inputs can be used as actuator button or bus button.
Input as bus button
Input as actuator button
If the input to the control of the device is used at this channel, then specify the button
function.
Time basis
0.1 s • 1 s • 1 min • 1 h
Time factor
4...255; 10
Staircase light time can
not be triggered again • can be triggered
again
Off telegram during staircase light period
affects
nothing • direct turn off
Blocking function blocks for
0 • 1
Value of the blocking object
after reset and ETS download
0 • 1
Response when blocking
no change • opened • closed
Response upon release
follows switch command • opened • closed
Operating mode
Use input 1 / 2 / 3 / 4
• no
• as a bus button
• as an actuator switch