19
Parameter setting
Actuator KNX S1R-B4 compact
• Version: 12.09.2022 • from application 1.0 • Technical changes and errors excepted.
Actuator as master:
For non-receipt of Slave status object move in secure position.
(
Actuator as slave:
For non-receipt of Master status object move in secure position.
Reference travel direction:
If the travel range is limited, the direction of the reference travel is fixed (safe position).
The direction can be set without limiting the travel range.
Blocking objects:
The output channel can be blocked in case of rain, wind or other events. The manual
operation is then not possible. Blocking and monitoring are configured here first. For
setting the individual blocks, separate menu items "Blocking X" will appear (see
chapter
The priorities of the blocking objects correspond to the sequence listed (Block 1 has the
highest priority, Block 5 the lowest).
Zero position sensor
• using communication object
• using input channel
• do not use
Actuator is
master • slave
Actuator is
master
Send repetition for master command in sec
1 … 255; 10
Monitoring period for slave status (and
zero position) object in sec
1 … 255; 10
Actuator is
slave
Send repetition for slave commands in sec
1 … 255; 10
Monitoring period for master status (and
zero position) object in sec
1 … 255; 10
Movement position for slave in % if
input "Master zero position command" = 1
0 … 100
Direction of reference travel
• in safe position
• in closed position
(move out shading)
• in open position
(window)
• shortest route
Use Block 1 (high priority)
• no
• yes, with blocking object
• yes, as wind blocking
• yes, as rain blocking
Use block 2
• no
• yes, with blocking object
• yes, as wind blocking
• yes, as rain blocking