30
Parameter setting
Actuator KNX S1R-B4 compact
• Version: 12.09.2022 • from application 1.0 • Technical changes and errors excepted.
For shutters the angle of the slats can be firmly set, or the slats can automatically follow
the elevation. This rule applies: Slats are closed at 100%, horizontal at 50%.
The slats should
not
follow the elevation (fixed reversing angle):
Adjust the desired position of the slats and the curtain.
The slats shall follow the elevation:
Three different elevation ranges can be set. A fixed curtain and slat position is specified
for each.
Moving position (for awnings and blinds):
------------------------------
Use teaching object for new shading position
: The curtain position it can be
specified numerically or taught manually. For teaching set "use teaching object: Yes"
and the "channel X shading position teaching object" is used for saving the position
reached. Saving occurs for value = 1 and can for example be realized via a button linked
to the teaching object. Numerical specifications already set are overwritten by the
teaching object.
Should the slats follow the elevation
no • yes
Should the slats follow the elevation
no
Slat position in %
0 … 100; 75
Shutter position in %
0 … 100; 75
Use teaching object for new shading
position
(curtain and slat positions will be saved,
see info below)
no • yes
Should the slats follow the elevation
yes
For an elevation less than (in degrees)
0 … 90; 10
Slat position in %
0 … 100; 95
For an elevation less than (in degrees)
0 … 90; 30
Slat position in %
0 … 100; 80
For an elevation less than (in degrees)
0 … 90; 45
Slat position in %
0 … 100; 65
For an elevation less than (in degrees)
90
Slat position in %
0 … 100; 50
Shutter position in %
0 … 100; 75
Use teaching object for new shading
position
(only the curtain position will be saved, see
info below)
no • yes
Awning position in % or
blind position in %
0 … 100; 75
Use teaching object for new shading
position
no • yes