Automatic settings
Control System WS1 Color / WS1000 Color
• Version: 14.12.2016 • Technical changes and errors excepted.
The automatic gutter heating functions can be accessed by pressing the buttons:
Now you can select individual roof gutter heatings and adjust their settings. For each
heating the following settings can be changed:
Use the arrow keys to set the temperature range within which the roof gutter heating
will be switched on. If the temperatures are very cold, no condensate forms and the
heating can remain switched off. Default setting: 5.0°C to -5.0°C.
Confirm your setting with the
OK
button.
Press the button to enable or disable the switchover to automatic mode at a set point
in time, or following a manual intervention.
The general Automatic Reset occurs daily at the same time.
Switching on: To set the gutter heating to Automatic at a set point in time, select
Yes
(this is the default setting).
Switching off: To switch off the gutter heating’s Reset function, select
No
.
Alternatively, the automatic function can be reactivated at a set time following a man-
ual intervention.
Switching on: To perform an Automatic Reset after a manual intervention, select
Yes
.
Switching off: To switch off the gutter heating’s Reset function, select
No
(this is the
default setting).
Confirm your setting with the
OK
button.
Automatic Reset time and/or period can be set.
System > Automatic Settings > General Settings > Automatic Reset
3.3. Define automatic reset
3.1.12.Set up alarm
You can select the alarm source which should activate the alarm output relay here. The
alarm settings can be accessed by pressing the buttons:
Automatic
Settings
Gutter Heating
System
Temperature Range
Automatic Reset
Automatic
Settings
Alarm
System