User Manual
Condor 415U-1-Cx Battery Powered Wireless IO
Version 1.4
31
Successfully loaded config from USB Drive.
Press any key to continue...
Read from USB memory device
has been completed and
configuration stored in 415U-1-Cx
Diagnostics
The 415U-1-Cx has a range of diagnostics available from the configuration menu to allow the
commissioning or to fault find of a system.
There is also a range of internal sensor diagnostic inputs available to allow mapping of critical
diagnostics back through the access point to SCADA or DCS systems. See sensor inputs section of this
user manual.
Diagnostic menu options
The diagnostic menu is access from the main menu and is summarized below:
Unit Diagnostic Menu:
a) Show I/O Values
Display internal inputs, Battery Voltage, Solar/Supply
Voltage, RSSI, Internal Temperature, Internal Status and
also current external input values for discrete, pulsed and
analog inputs. Will force analog loop supply to turn on to
sample fresh values.
b) Show Outputs
Allows you to manually turn on/off the outputs, Output
number turns it on and zero turns it all off.
c) SDI-12 value & Test
Test functions for SDI-12 sensor to allow
reading/changing of sensor address, info commands, etc.
to allow fault diagnosis.
d) Modbus Testing
Test the Modbus functionality, you will need to have a
Modbus device and I/O point configured to get access to
this menu.
e) Show Last connection/status
Displays the Status and last connection details
f) Test Mode Send Message
Force sending of Multi-sensor report message.
g) Show Firmware Version
Display Firmware versions of host, bootloader and radio.
h) Show Hardware Version
Display hardware revision of host electronics printed
circuit board assembly.
i) Activate BLE DFU
Turn on Bluetooth (BLE) configuration port
–
FUTURE
j) Update Host Bootloader
Upload new firmware into the host bootloader.
k) Calibrate Analog Input 1
Calibrate analog input 1
–
requires precision 4-20mA
source.
l) Calibrate Analog Input 2
Calibrate analog input 2
–
requires precision 4-20mA
source.
m) Set Analog Default Calibration
Reset analog inputs 1 and 2 to factory defaults.
n) Erase Flash Memory
Erase all flash memory
–
logged data, factory calibration
and configuration.
o) Enable Debug Console Output
Turn on diagnostic messages
p) Enable Monitor Radio Comms
Enable radio communication monitor
q) Return to Main Menu
Return to Main Menu