User Manual
Condor 415U-1-Cx Battery Powered Wireless IO
Version 1.4
19
See below for an example of the I/O and the use of multipliers.
I/O Quick Setup Mapping example for configuration of 3 stations:
Configuration Values
Example Units
Input Name
Input
Type
Register
Values
Register Type
Remote 1
Multiplier
Remote 3
Multiplier
Remote 10
Multiplier
Discrete input 1
Pulsed
37011
Unsigned 32 Bit
37011
37031
37101
Discrete input 2
Pulsed
37013
Unsigned 32 Bit
37013
37033
37103
Discrete input 3
ON/OFF
15010
Unsigned 16 Bit
15010
15030
15100
Discrete input 4
ON/OFF
15011
Unsigned 16 Bit
15011
15031
15101
Analog Input 1
4-20mA
35010
Unsigned 16 Bit
35010
35030
35100
Analog Input 2
4-20mA
35011
Unsigned 16 Bit
35011
35031
35101
Battery
Vdc
39011
Float
39011
39031
39101
Sup/Sol
Vdc
39013
Float
39013
39033
39103
RSSI
dBm
39015
Float
39015
39035
39105
Status
Bit Field
35012
Unsigned 16 Bit
35012
35032
35102
Access Point Register (REG) Address Values
If manually configuring the AP register it is recommended for application to use the standard Modbus
convention for REG address values used in the application. REG values can be set to a value up to a
maximum of 65535 and a value of 0 (zero) is used to disable a sensor REG where it is not used so that
no data is transmitted.
Below is a listing of REG address ranges that are recommended for use in a 415U-E-Cx or 415U-2-Cx
units when used as the AP for the 415U-1-Cx unit.
Input Type
REG Address Range
REG Area
Value Type
Discrete inputs
10406-20000
General Purpose Bit Storage
Single bit
Word Inputs
32256-36000
General Purpose Word Storage
Unsigned 16 bit
Long Inputs
36001-38000
General Purpose 32-bit Storage
Unsigned 32 bit
Float Inputs
38001-40000
General Purpose Floating Storage
Float 32 bit
Sensor input configuration is best completed after you have configured the Unit Config and
Communications as selected from main menu. It is recommended to use the I/O Quick Setup in the
Unit Config menu as well as it is a very fast way to setup basic IO configuration.
Once you have this basic setup completed then access the input setup through I/O Setup option from
main menu. This menu is displayed as shown below.
The current status of inputs will be displayed in the header of this menu. Sensor ID of 255 is used to
disabled/unused sensor and will have values that are bracketed with # and ID indicated with
–
as
shown below.
External Inputs
DI1
DI2
DI3
DI4
AI1
AI2
REG
37031
37013
15010
15011
35010
35011
Format
U-4
U-4
ELPRO
ELPRO
ELPRO
ELPRO
Raw
0
0
On
Off
0 mA
0 mA
Value
0
0
65535
0
8192
8192
External Outputs
DO1
DO2
Mode
ON/OFF
ON/OFF
REG
10001
10008
Sens
100
100
Value
0
0
I/O Setup Menu: